| Plan Review Notes For Permit 21021449 |
| Permit Number |
21021449 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-16 15:02:46 | 1- CONTRACTOR SUBMITTED 3 HARD COPIES OF WRONG PLAN. | | | THIS IS A FIRE ALARM PERMIT. PLAN SUBMITTED IS A FIRE | | | PROTECTION PLAN FP-1. SUBMIT THE TWO FIRE ALARM PLANS | | | SUBMITTED FOR REVIEW. | | | PLANS TO HAVE THE ENGINEER'S ORIGINAL SEAL/SIGNATURE. | | | AS REQUIRED BY 471 F.S. WHEN SUBMITTING PLANS | | | /DOCUMENTS FOR PUBLIC RECORDS. PLANS CAN BE UPLOADED TO | | | PROJECTDOX WITH DIGITAL SIGNATURE OR HARD COPIES WITH | | | ENGINEER'S ORIGINAL SIGNATURE/SEAL MAY BE DROPPED OFF | | | IN CITY HALL. | | | | | | 2- DRAWINGS UPLOADED TO PROJECTDOX "SIGNATURE" FOLDER | | | HAVE AN ENGINEER'S SELF CERTIFIED DIGITAL SIGNATURE. | | | ENGINEER CAN NOT SELF CERTIFY THE DIGITAL SIGNATURE. | | | THIRD PARTY CERTIFICATION IS REQUIRED BY FAC | | | 61G15-23.004. PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH | | | VALID ENGINEER'S DIGITAL SIGNATURE. OR SUBMIT HARD | | | COPIES WITH ORIGINAL SIGNATURE/SEAL. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|