Plan Review Notes
Plan Review Notes For Permit 21021449
Permit Number 21021449
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2021-03-16 15:02:461- CONTRACTOR SUBMITTED 3 HARD COPIES OF WRONG PLAN.
 THIS IS A FIRE ALARM PERMIT. PLAN SUBMITTED IS A FIRE
 PROTECTION PLAN FP-1. SUBMIT THE TWO FIRE ALARM PLANS
 SUBMITTED FOR REVIEW.
 PLANS TO HAVE THE ENGINEER'S ORIGINAL SEAL/SIGNATURE.
 AS REQUIRED BY 471 F.S. WHEN SUBMITTING PLANS
 /DOCUMENTS FOR PUBLIC RECORDS. PLANS CAN BE UPLOADED TO
 PROJECTDOX WITH DIGITAL SIGNATURE OR HARD COPIES WITH
 ENGINEER'S ORIGINAL SIGNATURE/SEAL MAY BE DROPPED OFF
 IN CITY HALL.
  
 2- DRAWINGS UPLOADED TO PROJECTDOX "SIGNATURE" FOLDER
 HAVE AN ENGINEER'S SELF CERTIFIED DIGITAL SIGNATURE.
 ENGINEER CAN NOT SELF CERTIFY THE DIGITAL SIGNATURE.
 THIRD PARTY CERTIFICATION IS REQUIRED BY FAC
 61G15-23.004. PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH
 VALID ENGINEER'S DIGITAL SIGNATURE. OR SUBMIT HARD
 COPIES WITH ORIGINAL SIGNATURE/SEAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  