Plan Review Notes
Plan Review Notes For Permit 21021445
Permit Number 21021445
Review Stop B
Sequence Number 3
Notes
Date Text
2021-09-28 09:29:08NEW 2 STORY APT. BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE THE FRONT PAGES FOR THE NANAWALL DOOR
 FLORIDA PRODUCT APPROVAL.
  
 2) ROOFING PRODUCT APPROVAL (NOA 20-0518.02) IS HIGH
 LIGHTED FOR A ROOFING SYSTEM THAT IS FOR A WOOD DECK
 WITH INSULATION ON TOP OF THE WOOD DECK - THE PLANS DO
 NOT SHOW ROOF INSULATION ADDED TO THE WOOD DECK. PLEASE
 PICK A ROOFING SYSTEM FOR - WOOD DECK NON INSULATED.
  
 3) ACCESSIBLE RESTROOM IN THE COFFEE SHOP - YOU NEED TO
 SHOW THE 18" BESIDE THE LATCH SIDE OF THE DOOR (SINK
 CANNOT BE WITHIN THE 18") - PLEASE SHOW THE DOOR
 MANEUVERING SPACE FROM THE INSIDE OF THE RESTROOM IN
 THE COFFEE SHOP TO COMPLY WITH FBC A404.2.4.1
  
 4) NEW COMMENT - FBC 1208.4 EFFICIENCY DWELLING UNITS.
 (2).THE UNIT SHALL BE PROVIDED WITH A SEPARATE CLOSET.
 - SORRY, I MISSED THIS REQUIREMENT.
  
  
 5) FOR THE HARD SURFACE FLOORING - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
  
  
  
  
  
  
  