| 2021-07-06 16:34:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PLAN SHEETS A4.1, P1.1, P1.2, P2.0, P2.1, P2.2, P3.1 |
| | HAVE BEEN RED LINED FOR YOUR USE TO HELP CLARIFY |
| | ISSUES. |
| | |
| | 1.COMPLIED |
| | |
| | 2.COMPLIED |
| | |
| | 3.COMPLIED BUT NEEDS FURTHER CLARIFICATION ON A4.1. NEW |
| | COMMENT: REFER TO RED-LINED A4.1 DETAIL 5 AND 6; PER |
| | WPB FBC 107.2.1, REMOVE NOTE "PAINTED MOISTURE |
| | RESISTANT GYP. BD. REFER TO FINISH SCHEDULE" AND |
| | REPLACE WITH "MOISTURE RESISTANT GYP. BD. W/FRP AND |
| | PAINT. REFER TO A10.0; ROOM FINISH SCHEDULE" |
| | |
| | 4. GRAB & GO COFFEE BAR: A THREE COMPARTMENT SINK IS |
| | SHOWN ON ARCHITECTURAL AND PLUMBING FLOOR PLANS BUT IS |
| | NOT NOTED ON THE PLUMBING FIXTURE SCHEDULE. PER WPB FBC |
| | 107.2.1, NOTE ON SCHEDULE AND IDENTIFY ON WATER AND |
| | SANITARY RISER DIAGRAMS. |
| | RESPONSE: SEE P1.1, P1.2, P3.1 |
| | NEW COMMENT: P1.1, P1.2 HAVE NOT BEEN REVISED ACCORDING |
| | TO THE REVISION COMMENT BOX AND DO NOT ADDRESS A |
| | DESIGNATION FOR THE THREE COMPARTMENT SINK (P-4H AS |
| | NOTED ON REVISED P3.1); P3.1 HAS BEEN REVISED AND |
| | REFLECTS THE THREE COMPARTMENT SINK AS P4H.PLEASE NOTE |
| | THAT P2.0, P2.1 HAVE BEEN REVISED BUT DO NOT ADDRESS |
| | THE THREE COMPARTMENT SINK (P-4H AS NOTED ON REVISED |
| | P3.1). PER WPB FBC 107.2.1, ADDRESS P-4H (THREE |
| | COMPARTMENT SINK) ON P1.1, P1.2, P2.0, P2.1. |
| | |
| | 5. COMPLIED |
| | |
| | 6. A4.1: THERE IS A MOP SINK LOCATED IN THE GRAB & GO |
| | COFFEE BAR TOILET ROOM. NOTHING IS SHOWN IN THE |
| | PLUMBING FIXTURE CONNECTION SCHEDULE AND THERE IS NO |
| | PIPING SHOWN FOR WATER AND SANITARY. PER WPB FBC |
| | 107.2.1, CLARIFY. A MANUFACTURER'S SPECIFICATION IS |
| | REQUIRED FOR SINK AND FAUCET. |
| | RESPONSE: SEE P1.1, P1.2, P2.0, P2.1, P3.1 |
| | NEW COMMENT: P1.1, P1.2 HAVE NOT BEEN REVISED ACCORDING |
| | TO THE REVISION COMMENT BOX AND DO NOT ADDRESS THE MOP |
| | SINK(P-5 AS NOTED ON REVISED P3.1); P2.0, P2.1 HAVE |
| | BEEN REVISED BUT DO NOT ADDRESS THE MOP SINK(P-5 AS |
| | NOTED ON REVISED P3.1). P3.1 HAS BEEN REVISED AND |
| | REFLECTS THE MOP SINK AS P-5. PER WPB FBC 107.2.1, |
| | ADDRESS P-5 MOP SINK ON P1.1, P1.2, P2.0, P2.1. |
| | |
| | 7.NEW COMMENT: IT IS NOTED THAT ALL CODE REFENCES FOR |
| | REQUIREMENTS NOTED BELOW HAVE BEEN ACKNOWLEDGED ON A4.1 |
| | ADA RESTROOM LEGEND. SOME REQUIREMENTS HAVE BEEN |
| | EXPLICITLY ADDRESSED, OTHERS HAVE NOT BEEN. PLEASE |
| | REVIEW RED-LINED A4.1 AND PER WPB FBC 107.2.1 REVISE |
| | FOR CLARIFICATION AS IS APPLICABLE. |
| | |
| | 8.COMPLIED |
| | |
| | 9. COMPLIED |
| | |
| | 10.NEW COMMENT. PER WPB FBC 107.2.1, PROVIDE DETAIL OF |
| | UL ASSEMBLY FOR VERTICAL CPVC RISERS THROUGH THE SECOND |
| | FLOOR. |
| | |
| | 11. COMPLIED |
| | C. GRAB & GO COFFEE BAR: THE THREE COMPARTMENT SINK IS |
| | NOW NOTED ON P3.1 AS P-4H; PER WPB FBC 107.2.1, NOTE |
| | IDENTIFY AS P-H4 ON WATER AND SANITARY PLAN VIEW AND |
| | RISER DIAGRAMS. |
| | . E. COMPLIED |
| | . F. THERE IS A MOP SINK LOCATED IN THE GRAB & GO |
| | COFFEE BAR TOILET ROOM. NOTHING IS SHOWN IN THE |
| | PLUMBING FIXTURE CONNECTION SCHEDULE AND THERE IS NO |
| | PIPING SHOWN FOR WATER AND SANITARY. PER WPB FBC |
| | 107.2.1, CLARIFY. A MANUFACTURER'S SPECIFICATION IS |
| | REQUIRED FOR SINK AND FAUCET. |
| | |
| | NEW COMMENT: MOP SINK P-5 IS NOW NOTED P3.1 PLUMBING |
| | FIXTURE CONNECTION SCHEDULE |
| | SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE ON P1.1 |
| | AND P2.0 A TRAPPED AND VENTED FIXTURE DRAIN FOR MOP |
| | SINK; CONNECT DOWNSTREAM OF BATHROOM WET VENT. NOTE P-5 |
| | FIXTURE DESIGNATION. COMPLY WITH REQUIREMENTS OF FBC PL |
| | CHAPTERS 7 AND 9. |
| | PER WPB FBC 107.2.1, PROVIDE ON P1.2 AND P2.1 HOT AND |
| | COLD WATER FOR MOP SINK. NOTE P-5 FIXTURE DESIGNATION. |
| | COMPLY WITH REQUIREMENTS OF FBC PL CHAPTER 6. INCLUDE |
| | IN SIZING CALCULATIONS. |
| | |
| | NEW COMMENT: 1-1/2 INCH WET VENT AT GRAB & GO COFFEE |
| | BAR TOILET ROOM SHALL BE SIZED 2 INCH AS IT IS A |
| | PORTION OF THE VENT STACK WHICH IS REQUIRED TO BE A |
| | MINIMUM 2 INCH SIZE PER FBC PL TABLE 906.1. |
| | 12. SECOND REQUEST: GRAB & GO COFFEE BAR: PER FBC PL |
| | 419.5, COLD OR TEMPERED WATER SHALL BE DELIVERED FROM |
| | LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC |
| | TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. SHOULD TEMPERED |
| | WATER BE PROVIDED, THEN PER WPB FBC 107.2.1, PROVIDE A |
| | SPECIFICATION AND A DETAIL. |
| | RESPONSE: REFER TO REVISED P2.1. |
| | P2.1 DOES NOT APPEAR TO ADDRESS. P1.2 WHICH HAS NOT |
| | BEEN REVISED ACCORDING TO THE REVISION COMMENT BOX NOW |
| | SHOWS AN IWH-2 WHICH IS NOT NOTED IN REVISED P3.1 |
| | PLUMBING FIXTURE CONNECTION SCHEDULE. P2.1 DOES SHOW AN |
| | IWH AT THE LAVATORY. THERE IS NOTHING TO INDICATE THAT |
| | A TEMPERED WATER DEVICE CONFORMING TO ASSE 1070 OR CSA |
| | B125.3, NOR A DETAIL AS REQUESTED. |
| | |
| | 13.COMPLIED |
| | SECOND REQUEST: AS CPVC IS TO BE ALLOWED THEN PER WPB |
| | FBC 107.2.1, PROVIDE A SPECIFICATION FOR HANGERS AND |
| | SUPPORTS THAT WILL MEET THE CRITERIA OF CPVC |
| | MANUFACTURER'S REQUIREMENTS FOR MATERIALS THAT MAY |
| | PHYSICALLY CONTACT THE CPVC MATERIAL PER FBC PL 301.7, |
| | 303.2 |
| | |
| | 14. COMPLIED |
| | |
| | 15. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE NOTE |
| | AT HANGER DETAIL "AS REQUIRED BY FBC PL 308.5, INTERVAL |
| | SUPPORT, PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH |
| | TABLE 308.5." |
| | |
| | 16. COMPLIED; SEE NEW COMMENTS AND RED LINED P2.0 AND |
| | P2.1 |
| | |
| | 17. NEW COMMENT: P1.1: PER FBC PL 708.1.4, A CLEANOUT |
| | IS NOT REQUIRED AT THE CHANGE IN DIRECTION IN THE |
| | SANITARY BUILDING DRAIN IN UNIT 102 AS IT IS |
| | ACCOMPLISHED WITH TWO (2) 45 DEGREE |
| | HOWEVER, PER FBC 708.1.1, A CLEANOUT IS REQUIRED AT THE |
| | END OF THE BUILDING DRAIN AND /OR BRANCHES OF THE |
| | BUILDING DRAIN. THIS CAN BE ACCOMPLISHED BY PROVIDING A |
| | CLEANOUT IN THE BASE OF THE SIX (6) SOIL STACKS OR |
| | CONTINUE THE BRANCH OF THE BUILDING DRAIN BEYOND THE |
| | STACK INTO THE CORRIDOR AND PROVIDE A FLOOR CLEANOUT |
| | SUITABLE FOR INTERIOR USE. PER WPB FBC 107.2.1, SHOW |
| | THE REQUIRED CLEANOUTS ON P1.1 AND P2.0. |
| | |
| | 18. P1.2: NOTE REFERS TO P1.0 TO CONTINUE. THERE IS NO |
| | P1.0. PER WPB FBC 107.2.1, CLARIFY. |
| | RESPONSE: REFER TO P1.1(ADDRESSES WASTE AND VENTS) |
| | P1.1NEW COMMENT: (ADDRESSES WASTE AND VENTS) HAS NOT |
| | BEEN REVISED ACCORDING TO THE REVISION COMMENT BOX AND |
| | THE NOTE REMAINS ON P1.2 (ADDRESSES WATER |
| | DISTRIBUTION). PER WPB FBC 107.2.1, CLARIFY. PLEASE |
| | NOTE THAT CIVIL WATER AND SEWER PLAN WS1 OF 4 SHOWS THE |
| | WATER METER AND BACKFLOW PREVENTER LOCATIONS THAT WOULD |
| | CORRESPOND WITH THE WATER SERVICE LOCATION ON P1.2; |
| | CIVIL WATER AND SEWER SERVICE DETAILS PLAN WS2 OF 4 |
| | PROVIDES STANDARD DETAIL WS-6 FOR THE APPLICABLE |
| | REQUIRED BACKFLOW PREVENTER. |
| | |
| | |
| | 19. COMPLIED; SEE NEW COMMENTS AND RED LINED P2.0 AND |
| | P2.1 |
| | |
| | 20. P2.0: PLUMBING RISER DIAGRAMS; DRAWINGS AND TEXT |
| | ARE NOT VERY CLEAR. PER WPB FBC 107.2.1.3, PROVIDE |
| | CLEAR, PRECISE INFORMATION. COMPLIED. |
| | |
| | NEW COMMENT: APT 106 BATHROOM WET VENT BEGINS 2 INCH AT |
| | THE LAVATORY, REDUCES AFTER CONNECTION WITH TUB 2 INCH |
| | FIXTURE DRAIN TO 1-1/2 INCH. SIZE TO BE 2 INCH PER FBC |
| | PL TABLE 912.3 AND FBC PL 704.2 |
| | |
| | NEW COMMENT: APT 105 BATHROOM WET VENT FROM LAVATORY TO |
| | BATHTUB IS 1-1/2 INCH SHALL BE SIZED 2 INCH PER FBC PL |
| | TABLE 906.1. |
| | |
| | NEW COMMENT: P-4, P-2, P-2H FIXTURE DRAINS ARE SHOWN |
| | RISING AT 45 DEGREES FROM THE POINT OF VENT BEFORE |
| | LEVELING OUT TO A HORIZONTAL PLANE AND CONNECTING TO |
| | THE TRAP WEIR. (SEE CHAPTER 2, DEFINITIONS: VERTICAL |
| | PIPE. ANY PIPE OR FITTING THAT MAKES AN ANGLE OF 45 |
| | DEGREES (0.79 RAD) OR MORE WITH THE HORIZONTAL.) |
| | PER FBC PL 902.2, THE TOTAL FALL IN A FIXTURE DRAIN DUE |
| | TO PIPE SLOPE SHALL NOT EXCEED THE DIAMETER OF THE |
| | FIXTURE DRAIN, NOR SHALL THE VENT CONNECTION TO A |
| | FIXTURE DRAIN, EXCEPT FOR WATER CLOSETS, BE BELOW THE |
| | WEIR OF THE TRAP. |
| | PER FBC PL 1002.3(5), S-TRAPS ARE PROHIBITED. |
| | |
| | NEW COMMENT: P2.0; SOME SOIL STACKS ARE SIZED 3 INCH |
| | AND SOME 4 INCH. ALL ARE TYPICALLY SERVICING A TYPICAL |
| | SECOND FLOOR BATHROOM. PER WPB FBC 107.2.1 AND |
| | 107.2.1.3, CLARIFY. |
| | |
| | NEW COMMENT: P2.0; WASTE STACK VENTS FOR KITCHEN SINKS |
| | SERVING UNITS 103/203 AND 104/204 SHALL BE SIZED 3 INCH |
| | PER FBC PL TABLE 913.4, TABLE 709.1, WPB FBC 107.2.1.3 |
| | |
| | 21. SECOND REQUEST: P2.0: SANITARY RISER DIAGRAM; |
| | IDENTIFY CLOTHES WASHER AND SHOW FIXTURE DRAIN PIPING, |
| | TRAP, WASTE BRANCH PIPING, VENT PIPING AND SIZE OF |
| | PIPING. PLEASE NOTE THAT P2.0 HAS BEEN REVISED BUT DOES |
| | NOT IDENTIFY THE CLOTHES WASHER AND DOES NOT SHOW |
| | FIXTURE DRAIN PIPING, TRAP, VERTICAL WASTE PIPING, VENT |
| | PIPING AND SIZE OF PIPING. |
| | |
| | 22.SECOND REQUEST. P2.0: SANITARY RISER DIAGRAM; WASTE |
| | STACK VENT FOR UNIT 106/206; 2-1/2 INCH SIZE SANITARY |
| | PIPING IS STILL SHOWN. MANUFACTURERS OF PVC DWV PIPE |
| | AND FITTINGS SUCH AS SUCH AS CHARLOTTE, NIBCO AND |
| | SPEARS DO NOT MANUFACTURE THIS SIZE PIPE AND FITTINGS |
| | THAT WOULD COMPLY WITH THE MATERIAL REQUIREMENTS OF FBC |
| | PL CHAPTER 7. THIS WASTE STACK VENT FOR KITCHEN SINKS |
| | MAY BE SIZED 3 INCH OR 2 INCH, BUT SHALL NOT BE 2-1/2 |
| | INCH. FBC PL TABLE 913.4, TABLE 709.1, WPB FBC |
| | 107.2.1.3. SIZE ACCORDINGLY. |
| | |
| | 23. SCHEDULE PROVIDED; SECOND REQUEST: CLEARLY IDENTIFY |
| | ON WATER RISER DIAGRAM P2.1 ALL WATER HAMMER ARRESTORS. |
| | TO BE CLEAR, PER WPB FBC 107.2.1, PROVIDE A DESIGNATION |
| | ON THE RISER DIAGRAM AT EACH WATER HAMMER ARRESTORS |
| | SHOWN I.E., WHA-AA, WHA-A COORDINATED WITH SCHEDULE. |
| | |
| | |
| | 24. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL |
| | AND SPECIFICATION FOR TRAP SEAL PROTECTION AS REQUIRED |
| | BY FBC PL 1002.4.1 FOR THE FLOOR DRAIN LOCATED IN THE |
| | GRAB & GO COFFEE BAR TOILET ROOM. SHOW COMPLIANCE WITH |
| | ONE OF THE FOLLOWING: FBC PL 1002.4.1.1, 1002.4.1.2, |
| | 1002.4.1.3 OR 1002.4.1.4. IF OTHER THAN 1002.4.1.4, |
| | SHOW PRIMER LINE INTO FLOOR DRAIN TRAP AND SOURCE |
| | LOCATION ON THE APPROPRIATE RISER DIAGRAMS AND FLOOR |
| | PLAN. |
| | RESPONSE: SEE UPDATED P3.1. |
| | COMMENT; NOTHING SHOWN. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | |
| | 25. WHEN REFERRING TO CIVIL DRAWINGS, PROVIDE CIVIL |
| | DRAWING PLAN SHEET NUMBER. IN THE CASE OF THE POTABLE |
| | WATER, SHOW THE BACKFLOW PREVENTER, REFER TO THE |
| | CORRECT CIVIL DRAWINGS FOR EXACT LOCATION AND FOR |
| | INSTALLATION DETAIL; NOTE TO PROVIDE BY OTHERS. A |
| | SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER; |
| | PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS. |
| | ACKNOWLEDGED BY DESIGNER BUT NOT ADDRESSED ON PLANS |
| | NEW COMMENTS |
| | PLEASE NOTE THAT CIVIL WATER AND SEWER PLAN WS1 OF 4 |
| | SHOWS WATER AND SEWER CONNECTIONS THAT WOULD CORRESPOND |
| | WITH THE TERMINATION POINTS ON P1.1, P1.2, P2.0, P2.1; |
| | PER WPB FBC 107.2.1, INDICATE AT TERMINATION POINTS ON |
| | THE PLAN SHEETS P1.1, P1.2, P2.0, P2.1. |
| | CIVIL PAVING, GRADING AND DRAINAGE PLAN PD1 OF 6 |
| | PROVIDES SITE STORM DRAINAGE BUT MAKES NO PROVISION FOR |
| | BUILDING STORM SEWER CONNECTION OR FOR A/C CONDENSATE |
| | CONNECTION. PER WPB FBC 107.2.1, FURTHER CLARIFICATION |
| | AND COORDINATION BETWEEN CIVIL AND PLUMBING PLANS (P1.1 |
| | AND P2.2) IS REQUIRED. |
| | CONDENSATE DRAIN MAY CONNECT TO SITE STORM, BUILDING |
| | STORM DRAIN/SEWER OR TO A DRYWELL. PER FBC 107.2.1, |
| | CLARIFY AND PROVIDE DETAIL. |
| | |
| | 26. COMPLIED |
| | |
| | 27. COMPLIED |
| | |
| | 28. COMPLIED |
| | |
| | 29. PER FBC PL 314 (M) 314.2, PLEASE INDICATE WHICH |
| | CIVIL SHEET AND THE DETAIL SHOWING THE LOCATION OF THE |
| | CONDENSATE DRAINAGE LOCATION AT THE EXTERIOR. SEE |
| | COMMENT 25 ABOVE REGARDING CIVIL DRAWINGS. |
| | |
| | 30 COMPLIED |
| | |
| | 31. COMPLIED |
| | |
| | 32. COMPLIED |
| | |
| | 33. COMPLIED |
| | |
| | 34. COMPLIED |
| | |
| | NEW COMMENTS |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR SIZING |
| | OF WATER DISTRIBUTION. |
| | |
| | 2. P2. 1 TYPICALLY SHOWS 3/4 INCH HOT FROM IWH TO ALL |
| | BATHROOM FIXTURES LEADING TO INEFFICIENT HEATING. |
| | PLEASE NOTE THAT FBC EC C404.5 LIMITS THE VOLUME OF |
| | WATER THAT MAY TRAVEL THROUGH A HOT WATER PIPE AND |
| | PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE SIZE TO |
| | ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED BEFORE |
| | HOT WATER REACHES THE OUTLET, THUS REDUCING ENERGY |
| | USAGE AS WELL AS THE WASTING OF WATER. PER WPB FBC |
| | 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND. REVISIT |
| | AND SIZE THE HOT WATER DISTRIBUTION ACCORDINGLY. |
| | |
| | 3. PER WPB FBC 107.2.1, PROVIDE NOTE "THE WASTE |
| | CONNECTION OF A RESIDENTIAL DISHWASHER SHALL CONNECT |
| | DIRECTLY TO A WYE BRANCH FITTING ON THE TAILPIECE OF |
| | THE KITCHEN SINK, DIRECTLY TO THE DISHWASHER CONNECTION |
| | OF A FOOD WASTE DISPOSER, OR THROUGH AN AIR BREAK TO A |
| | STANDPIPE. THE WASTE LINE OF A RESIDENTIAL DISHWASHER |
| | SHALL RISE AND BE SECURELY FASTENED TO THE UNDERSIDE OF |
| | THE SINK RIM OR COUNTER-TOP PER FBC PL 409.4.". |
| | |
| | 4.NEW COMMENT: P2.1; PER WPB FBC 107.2.1 CLEARLY |
| | IDENTIFY ALL FIXTURES AND APPLIANCES SERVICED IN THE |
| | RISER DIAGRAM AT THE POINT OF CONNECTION. |
| | |
| | 5.NEW COMMENT: P2.1, P1.2; P2.1 SHOWS HOT AND COLD |
| | WATER TO THE "HOUSE" WASHER SUPPLIED FROM UNIT 106 |
| | BATHROOM PARTITION WATER DISTRIBUTION. ADDITIONALLY, |
| | P1.2 INDICATES A IWH-1 WATER HEATER IS NOTED ON P1.2 ON |
| | THE WALL IN THE ELECTRICAL ROOM ADJACENT TO THE WASHER. |
| | THE WASHER IS NOT INTEGRAL TO UNIT 106. AS SHOWN ON |
| | P1.2, PROVIDE ON P2.1 A SEPARATE COLD WATER DOWN-FEED |
| | PIPE WITH FULL OPEN VALVE AT THE TOP TO SERVICE WASHER |
| | AND IWH-1 AHEAD OF THE FULL OPEN VALVE SERVICING UNIT |
| | 106 SO THAT HOUSE MAINTENANCE CAN SERVICE THE WASHER |
| | PLUMBING WITHOUT DISRUPTING SERVICE TO UNIT 106. FBC PL |
| | 606.1(6). PER WPB FBC 107.2.1, ADD IWH-1 TO PLUMBING |
| | FIXTURE CONNECTION SCHEDULE ON P3.1, SHOW ON RISER |
| | DIAGRAM AND COORDINATE LOCATION WITH ELECTRICAL. TO BE |
| | CLEAR, ELECTRICAL SHOWS NOTHING REGARDING IWH-1 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | AN ATTEMPT HAS BEEN MADE TO MAKE THE MOST COMPREHENSIVE |
| | REVIEW POSSIBLE USING THE PLANS PROVIDED. A REVIEW OF |
| | RESUBMITTED PLANS MAY RESULT IN ADDITIONAL COMMENTS. |
| | PLEASE RESUBMIT CLEARLY LEGIBLE PLANS; A RESPONSE |
| | NARRATIVE ADDRESSING THE COMMENTS FROM THE PRIOR REVIEW |
| | WILL GREATLY HELP WITH THE REVIEW PROCESS AND IS VERY |
| | MUCH APPRECIATED. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS. PLEASE DO NOT HESITATE TO CALL. |
| | |
| | 21021445 3404 BROADWAY |
| | |