| Date |
Text |
| 2021-07-13 15:53:19 | NEW 2 STORY APT. BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE NANAWALL |
| | DOOR. |
| | 2) ROOFING PRODUCT APPROVAL ADDED TO FOLDER (NOA |
| | 20-0518.02) PLEASE CIRCLE THE ROOFING "SYSTEM TYPE" |
| | WITHIN THE PRODUCT APPROVAL TO BE USED. MAKING SURE |
| | THAT THE WIND PRESSURES FOR THE SYSTEM CHOSEN MEETS THE |
| | REQUIRED WIND DESIGN PRESSURES OR PROVIDE THE |
| | ADDITIONAL ROOFING ATTACHMENT DETAILS FROM AN ARCHITECT |
| | OR ENGINEER - PLEASE SEE GENERAL LIMITATIONS IN THE |
| | PRODUCT APPROVAL. |
| | 3) ROOFING PRODUCT APPROVAL FL5293 R39 IS EXPIRED |
| | PLEASE PROVIDE THE UPDATED VERSION FL5293 R44 AND THE |
| | UPDATED INSTALLATION INSTRUCTIONS. (UP DATED VERSION |
| | HAS NOT BEEN PROVIDED PERHAPS (NOA 20-0518.02) IS TO |
| | TAKE ITS PLACE? |
| | 4) PLEASE SHOW THE BOTTOM RAMP LANDING DIMENSIONS TO |
| | COMPLY WITH FBC A405.7 - - 405.7.3 LENGTH. |
| | THE LANDING CLEAR LENGTH SHALL BE 60 INCHES (1525 MM) |
| | LONG MINIMUM. |
| | 5) PLEASE PROVIDE A DETAIL SHOWING THE TOP OF THE UNIT |
| | SEPARATION WALL AT THE ROOF SHEATHING OF THE 2ND FLOOR. |
| | FBC 708.4 (BETWEEN UNIT 205 AND UNIT 206) (FIRE |
| | BLOCKING) |
| | 6) PLEASE SHOW THE ATTIC VENTILATION TO COMPLY WITH FBC |
| | 1203.2 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND |
| | BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH |
| | THE MOVEMENT OF AIR. AN AIRSPACE OF NOT LESS THAN 1 |
| | INCH (25 MM) SHALL BE PROVIDED BETWEEN THE INSULATION |
| | AND THE ROOF SHEATHING. THE NET FREE VENTILATING AREA |
| | SHALL BE NOT LESS THAN 1/150 OF THE AREA OF THE SPACE |
| | VENTILATED. VENTILATORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. |
| | 7) PLEASE SHOW THE ACCESSIBLE RAMP HAND RAIL EXTENSIONS |
| | TO COMPLY WITH FBC A505.10.1 (TOP EXTENSIONS ARE NOT |
| | SHOWN) TOP AND BOTTOM EXTENSION AT RAMPS. |
| | RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE |
| | LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP |
| | AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A |
| | WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE |
| | CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN. |
| | 8) PLEASE SHOW THE DOOR MANEUVERING SPACE FROM THE |
| | INSIDE OF THE RESTROOM IN THE COFFEE SHOP TO COMPLY |
| | WITH FBC A404.2.4.1 |
| | 9) PLEASE SHOW THE LAUNDRY ROOM TO BE ACCESSIBLE PER |
| | FBC A FAIR HOUSING SECTION 5 REQUIREMENT NUMBER 2 (SHOW |
| | THE CLEAR FLOOR SPACE). |
| | 10) COFFEE SHOP RESTROOM DOOR SWING INTO CLEAR FLOOR |
| | SPACE - FOR THE EXCEPTION THE EXTRA CLEAR FLOOR SPACE |
| | NEEDS TO BE CLEAR OF THE DOOR SWING - FBC A603.2.3 DOOR |
| | SWING.2.WHERE THE TOILET ROOM OR BATHING ROOM IS FOR |
| | INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE |
| | DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY |
| | FIXTURE. |
| | 11) DRAWING A4.1 SHOWS COFFEE SHOP RESTROOM ELEVATION |
| | SHOWS WALL AS DRYWALL - GENERAL NOTE SAYS DURA ROCK |
| | WALLS - PLEASE CLARIFY FBC 1210.2.2WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | 12) FOR THE HARD SURFACE FLOORING - THE FOLLOWING |
| | ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |