Plan Review Notes
Plan Review Notes For Permit 21021445
Permit Number 21021445
Review Stop B
Sequence Number 2
Notes
Date Text
2021-07-13 15:53:19NEW 2 STORY APT. BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE NANAWALL
 DOOR.
 2) ROOFING PRODUCT APPROVAL ADDED TO FOLDER (NOA
 20-0518.02) PLEASE CIRCLE THE ROOFING "SYSTEM TYPE"
 WITHIN THE PRODUCT APPROVAL TO BE USED. MAKING SURE
 THAT THE WIND PRESSURES FOR THE SYSTEM CHOSEN MEETS THE
 REQUIRED WIND DESIGN PRESSURES OR PROVIDE THE
 ADDITIONAL ROOFING ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER - PLEASE SEE GENERAL LIMITATIONS IN THE
 PRODUCT APPROVAL.
 3) ROOFING PRODUCT APPROVAL FL5293 R39 IS EXPIRED
 PLEASE PROVIDE THE UPDATED VERSION FL5293 R44 AND THE
 UPDATED INSTALLATION INSTRUCTIONS. (UP DATED VERSION
 HAS NOT BEEN PROVIDED PERHAPS (NOA 20-0518.02) IS TO
 TAKE ITS PLACE?
 4) PLEASE SHOW THE BOTTOM RAMP LANDING DIMENSIONS TO
 COMPLY WITH FBC A405.7 - - 405.7.3 LENGTH.
 THE LANDING CLEAR LENGTH SHALL BE 60 INCHES (1525 MM)
 LONG MINIMUM.
 5) PLEASE PROVIDE A DETAIL SHOWING THE TOP OF THE UNIT
 SEPARATION WALL AT THE ROOF SHEATHING OF THE 2ND FLOOR.
 FBC 708.4 (BETWEEN UNIT 205 AND UNIT 206) (FIRE
 BLOCKING)
 6) PLEASE SHOW THE ATTIC VENTILATION TO COMPLY WITH FBC
 1203.2 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND
 BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH
 THE MOVEMENT OF AIR. AN AIRSPACE OF NOT LESS THAN 1
 INCH (25 MM) SHALL BE PROVIDED BETWEEN THE INSULATION
 AND THE ROOF SHEATHING. THE NET FREE VENTILATING AREA
 SHALL BE NOT LESS THAN 1/150 OF THE AREA OF THE SPACE
 VENTILATED. VENTILATORS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
 7) PLEASE SHOW THE ACCESSIBLE RAMP HAND RAIL EXTENSIONS
 TO COMPLY WITH FBC A505.10.1 (TOP EXTENSIONS ARE NOT
 SHOWN) TOP AND BOTTOM EXTENSION AT RAMPS.
 RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP
 AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A
 WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
 8) PLEASE SHOW THE DOOR MANEUVERING SPACE FROM THE
 INSIDE OF THE RESTROOM IN THE COFFEE SHOP TO COMPLY
 WITH FBC A404.2.4.1
 9) PLEASE SHOW THE LAUNDRY ROOM TO BE ACCESSIBLE PER
 FBC A FAIR HOUSING SECTION 5 REQUIREMENT NUMBER 2 (SHOW
 THE CLEAR FLOOR SPACE).
 10) COFFEE SHOP RESTROOM DOOR SWING INTO CLEAR FLOOR
 SPACE - FOR THE EXCEPTION THE EXTRA CLEAR FLOOR SPACE
 NEEDS TO BE CLEAR OF THE DOOR SWING - FBC A603.2.3 DOOR
 SWING.2.WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
 11) DRAWING A4.1 SHOWS COFFEE SHOP RESTROOM ELEVATION
 SHOWS WALL AS DRYWALL - GENERAL NOTE SAYS DURA ROCK
 WALLS - PLEASE CLARIFY FBC 1210.2.2WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
 12) FOR THE HARD SURFACE FLOORING - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
  
  
  
  
  
  
  