Plan Review Notes
Plan Review Notes For Permit 21021445
Permit Number 21021445
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-29 15:23:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE: CS-COVER PAGE: CODE ANALYSIS/BUILDING CODES.
 COMPLIANCE WITH THE FLORIDA BUILDING CODE, PLUMBING
 2020 AND FLORIDA BUILDING CODE, ACCESSIBILITY 2020 IS
 REQUIRED. PER WPB FBC 107.2.1, NOTE IN CS-COVER PAGE:
 CODE ANALYSIS/BUILDING CODES.
  
 2.A4.1 GRAB & GO COFFEE BAR: THE BUILDING IS CLASSIFIED
 R2, SEEMS TO CONFORM TO FBC PL TABLE 403.1/RESIDENTIAL/
 APARTMENT HOUSE. THE RETAIL FOOD SPACE, GRAB & GO
 COFFEE BAR SHOULD BE CLASSIFIED MERCANTILE. PER WPB FBC
 107.2.1, CLARIFY.
  
 3.A4.1 GRAB & GO COFFEE BAR: PER WPB FBC 107.2.1,
 PROVIDE FINISH WALL SCHEDULE FOR THE COFFEE SHOP
 RESTROOM AND REVISE ADA BATHROOM DETAILS 5 AND 6 ON
 A4.1 TO COMPLY WITH FBC PL 310.3 AND FBC 1210.2.2.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT
 THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS
 THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE
 THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD
 BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 4. GRAB & GO COFFEE BAR: A THREE COMPARTMENT SINK IS
 SHOWN ON ARCHITECTURAL AND PLUMBING FLOOR PLANS BUT IS
 NOT NOTED ON THE PLUMBING FIXTURE SCHEDULE. PER WPB FBC
 107.2.1, NOTE ON SCHEDULE AND IDENTIFY ON WATER AND
 SANITARY RISER DIAGRAMS.
  
 5. FIXTURES P-1H AND P-2H ARE NOTED ON THE PLUMBING
 PLANS BUT NOT ON THE PLUMBING FIXTURE CONNECTION
 SCHEDULE. PER WPB FBC 107.2.1, CLARIFY.
  
 6. A4.1: THERE IS A MOP SINK LOCATED IN THE GRAB & GO
 COFFEE BAR TOILET ROOM. NOTHING IS SHOWN IN THE
 PLUMBING FIXTURE CONNECTION SCHEDULE AND THERE IS NO
 PIPING SHOWN FOR WATER AND SANITARY. PER WPB FBC
 107.2.1, CLARIFY. A MANUFACTURER'S SPECIFICATION IS
 REQUIRED FOR SINK AND FAUCET.
  
 7. A4.1: COMPLIANCE WITH FLORIDA BUILDING CODE,
 ACCESSIBILITY 2020 IS REQUIRED. ADAAG IS NOT APPLICABLE
 TO THIS SPACE. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE
 WITH FBC ACC CHAPTERS 2, 3 AND 6 AND PROVIDE ON THE
 PLAN AND ELEVATION DETAILS FOR NEW TOILET ROOM
 INDICATING THE FOLLOWING:
 . A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 . B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 . C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 . D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 . E. FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 . F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 . G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 . H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE.
 . I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 . J. SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2.
 . K. PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 . L. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 . M. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
  
 8. A4.1: REGARDING THE THREE-COMPARTMENT SINK, PLEASE
 NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT
 NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC
 ACC 212.3. PER WPB FBC 107.2.1, PROVIDE ON DETAIL 9,
 THE REQUIRED DIMENSIONS TO SHOW COMPLIANCE WITH FBC ACC
 606.3.
  
 9. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 611.4, PROVIDE DETAIL FOR ACCESSIBLE CLOTHES WASHER.
 TOP LOADING MACHINES SHALL HAVE THE DOOR TO THE LAUNDRY
 COMPARTMENT LOCATED 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR. FRONT LOADING MACHINES SHALL HAVE THE
 BOTTOM OF THE OPENING TO THE LAUNDRY COMPARTMENT
 LOCATED 15 INCHES (380 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR.
  
 10.PER WPB FBC 107.2.1, PROVIDE DETAILS OF UL
 ASSEMBLIES FOR HORIZONTAL AND VERTICAL PIPE
 PENETRATIONS IN FIRE RATED STRUCTURES. ASSEMBLIES SHALL
 BE APPLICABLE TO THE SPECIFIED PIPESIZES, MATERIALS AND
 AFFECTED STRUCTURES. COMPLY WITH FBC CHAPTER 7.
  
 11.P3.1 PLUMBING FIXTURE CONNECTION SCHEDULE
 . A. REVISE NOTE 1 TO STATE "PER FBC PL 412.3,
 INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION VALVES
 SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. THEY SHALL BE EQUIPPED
 WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF THE VALVE
 TO 120F (49C), WHICH SHALL BE FIELD ADJUSTED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 IN-LINE THERMOSTATIC VALVES SHALL NOT BE UTILIZED FOR
 COMPLIANCE WITH THIS SECTION."
 . B. NOTE 4 PERTAINS TO BIDET, NONE SHOWN IN SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, DELETE ANY
 REFERENCE TO THE FBC RES CODE AS THIS PROJECT IS
 REQUIRED TO COMPLY WITH THE FLORIDA BUILDING CODE,
 PLUMBING 2020.
 . C. GRAB & GO COFFEE BAR: A THREE COMPARTMENT SINK IS
 SHOWN ON ARCHITECTURAL AND PLUMBING FLOOR PLANS BUT IS
 NOT NOTED ON THE PLUMBING FIXTURE SCHEDULE. PER WPB FBC
 107.2.1, NOTE ON SCHEDULE AND IDENTIFY ON WATER AND
 SANITARY RISER DIAGRAMS.
 . E. FIXTURES P-1H AND P-2H ARE NOTED ON THE PLUMBING
 PLANS BUT NOT ON THE PLUMBING FIXTURE CONNECTION
 SCHEDULE. PER WPB FBC 107.2.1, CLARIFY.
 . F. THERE IS A MOP SINK LOCATED IN THE GRAB & GO
 COFFEE BAR TOILET ROOM. NOTHING IS SHOWN IN THE
 PLUMBING FIXTURE CONNECTION SCHEDULE AND THERE IS NO
 PIPING SHOWN FOR WATER AND SANITARY. PER WPB FBC
 107.2.1, CLARIFY. A MANUFACTURER'S SPECIFICATION IS
 REQUIRED FOR SINK AND FAUCET.
 . G. PROVIDE MANUFACTURER'S SPECIFICATION FOR ALL
 SCHEDULED PLUMBING FIXTURES.
  
 12. GRAB & GO COFFEE BAR: PER FBC PL 419.5, COLD OR
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. SHOULD TEMPERED WATER BE PROVIDED,
 THEN PER WPB FBC 107.2.1, PROVIDE A SPECIFICATION AND A
 DETAIL.
  
 13. DOMESTIC WATER MATERIAL SPECIFICATION CALLS FOR
 TYPE L COPPER WITH SWEAT FITTINGS AND NOTES THAT CPVC
 WILL BE ACCEPTABLE ONLY WITH OWNERSHIP APPROVAL. THESE
 PLANS WILL NOT BE APPROVED WITH CONTINGENCY FOR OWNER
 APPROVAL. IF CPVC IS TO BE ALLOWED THEN PER WPB FBC
 107.2.1, PROVIDE A SPECIFICATION FOR HANGERS AND
 SUPPORTS THAT WILL MEET THE CRITERIA OF CPVC
 MANUFACTURER?S REQUIREMENTS FOR MATERIALS THAT MAY
 PHYSICALLY CONTACT THE CPVC MATERIAL AS WELL AS A
 SPECIFICATION FOR VALVES. OTHERWISE, REMOVE THE NOTE
 THAT MIGHT ALLOW CPVC. THE SPECIFICATION FOR VALVES
 SHALL INCLUDE THE WORDS "LEAD FREE".
  
 14. PROVIDE A NOTE STATING ALL MATERIALS USED IN THE
 DOMESTIC WATER SYSTEM SHALL BE LEAD FREE.
  
 15. HORIZONTAL/VERTICAL SUPPORT PER WPB FBC 107.2.1,
 SPECIFY HANGER TYPE FOR EACH SPECIFIED MATERIAL AND
 SYSTEM. INCLUDE COATINGS FOR NON-FERROUS METAL PIPING.
 PROVIDE NOTE AT HANGER DETAIL "AS REQUIRED BY FBC PL
 308.5, INTERVAL SUPPORT, PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH TABLE 308.5."
  
 16. P1.1: PER WPB FBC 107.2.1, SIZE ALL PIPING.
  
 17. P1.1: PER FBC PL 708.1.4, A CLEANOUT IS REQUIRED AT
 THE CHANGE IN DIRECTION IN THE SANITARY BUILDING DRAIN
 IN UNIT 102. PER WPB FBC 107.2.1, SHOW ON FLOOR PLAN
 AND RISER DIAGRAM; PROVIDE DETAIL AND ADD TO DRAIN
 SCHEDULE.
  
 18. P1.2: NOTE REFERS TO P1.0 TO CONTINUE. THERE IS NO
 P1.0. PER WPB FBC 107.2.1, CLARIFY.
  
 19. P1.2: PER WPB FBC 107.2.1, SIZE ALL PIPING.
  
 20. P2.0: PLUMBING RISER DIAGRAMS; DRAWINGS AND TEXT
 ARE NOT VERY CLEAR. PER WPB FBC 107.2.1.3, PROVIDE
 CLEAR, PRECISE INFORMATION.
  
 21. P2.0: SANITARY RISER DIAGRAM; IDENTIFY CLOTHES
 WASHER AND SHOW FIXTURE DRAIN PIPING, TRAP, WASTE
 BRANCH PIPING, VENT PIPING AND SIZE OF PIPING.
  
 22. P2.0: SANITARY RISER DIAGRAM; 2-1/2 INCH SIZE
 SANITARY PIPING IS SHOWN. MANUFACTURERS OF PVC DWV PIPE
 AND FITTINGS SUCH AS SUCH AS CHARLOTTE, NIBCO AND
 SPEARS DO NOT MANUFACTURE THIS SIZE PIPE AND FITTINGS
 THAT WOULD COMPLY WITH THE MATERIAL REQUIREMENTS OF FBC
 PL CHAPTER 7. PER WPB FBC 107.2.1, SIZE ACCORDINGLY.
  
 23. PROVIDE WATER HAMMER ARRESTOR SCHEDULE WITH
 MANUFACTURER AND MODEL NUMBER; CLEARLY IDENTIFY ON
 WATER RISER DIAGRAM ALL WATER HAMMER ARRESTORS.
  
 24. PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR TRAP SEAL PROTECTION AS REQUIRED BY
 FBC PL 1002.4.1 FOR THE FLOOR DRAIN LOCATED IN THE GRAB
 & GO COFFEE BAR TOILET ROOM. SHOW COMPLIANCE WITH ONE
 OF THE FOLLOWING: FBC PL 1002.4.1.1, 1002.4.1.2,
 1002.4.1.3 OR 1002.4.1.4. IF OTHER THAN 1002.4.1.4,
 SHOW PRIMER LINE INTO FLOOR DRAIN TRAP AND SOURCE
 LOCATION ON THE APPROPRIATE RISER DIAGRAMS AND FLOOR
 PLAN.
  
 25. WHEN REFERRING TO CIVIL DRAWINGS, PROVIDE CIVIL
 DRAWING PLAN SHEET NUMBER. IN THE CASE OF THE POTABLE
 WATER, SHOW THE BACKFLOW PREVENTER, REFER TO THE
 CORRECT CIVIL DRAWINGS FOR EXACT LOCATION AND FOR
 INSTALLATION DETAIL; NOTE TO PROVIDE BY OTHERS. A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER;
 PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS.
  
 26. FBC PL 314 (M) 314.2, PLEASE PROVIDE NOTES ON THE
 CONDENSATE DRAWING INDICATING THE PIPING MAINTAIN A
 MINIMUM HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE
 OF NOT LESS THAN ONE-EIGHTH UNIT IN 12 UNITS HORIZONTAL
 (1 PERCENT SLOPE).
  
 27. PER FBC PL 314 (M) 314.2.4.1, PLEASE SHOW THE
 INLINE CHECK VALVE OR TRAP AT EACH FCU CONDENSATE LINE.
  
 28. PER FBC PL 314 (M) 314.2.5, MAIN PIPING SHALL BE
 SIZED AND FITTINGS SHALL BE CONFIGURED (I.E.
 COMMERCIALLY MANUFACTURED DRAINAGE PATTERN) TO ALLOW
 RODDING BY COMMERCIALLY MANUFACTURED DRAIN CLEARING
 EQUIPMENT. SHOW LOCATIONS OF ALL CLEANOUTS. SPACE
 CLEANOUTS AT INTERVALS THAT WILL ACCOMMODATE SAID
 EQUIPMENT.
  
 29. PER FBC PL 314 (M) 314.2, PLEASE INDICATE WHICH
 CIVIL SHEET AND THE DETAIL SHOWING THE LOCATION OF THE
 CONDENSATE DRAINAGE LOCATION AT THE EXTERIOR. FBC M
 307.2.1
  
 30. PER FBC PL 314 (M) 314.2.3, (M) 314.2.3.1, PLEASE
 SHOW THE SECONDARY DRAIN OR SHOW THE WATER MONITORING
 DEVICE FOR EACH FCU.
  
 31. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS USED IN
 SIZING OF STORM DRAINS (TABLES FROM FBC PL 1106.2,
 INDICATE SLOPE OF HORIZONTAL DRAINS AND NOTE HOW MUCH
 SQUARE FOOTAGE IS ATTRIBUTED TO PARAPET WALLS)
  
 32. P1.3: THE SCUPPERS CALCULATION TABLE BASED ON 2014
 FBC-PL TABLE 1106.7 SHALL NOT BE USED. FBC PL 1106.5
 STATES WHERE SCUPPERS ARE USED FOR PRIMARY ROOF
 DRAINAGE OR FOR SECONDARY (EMERGENCY OVERFLOW) ROOF
 DRAINAGE OR BOTH, THE QUANTITY, SIZE, LOCATION AND
 INLET ELEVATION OF THE SCUPPERS SHALL BE CHOSEN TO
 PREVENT THE DEPTH OF PONDING WATER ON THE ROOF FROM
 EXCEEDING THE MAXIMUM WATER DEPTH THAT THE ROOF WAS
 DESIGNED FOR AS DETERMINED BY SECTION 1611.1 OF THE
 FLORIDA BUILDING CODE, BUILDING. SCUPPER OPENINGS SHALL
 BE NOT LESS THAN 4 INCHES (102 MM) IN HEIGHT AND HAVE A
 WIDTH THAT IS EQUAL TO OR GREATER THAN THE
 CIRCUMFERENCE OF A ROOF DRAIN SIZED FOR THE SAME ROOF
 AREA. THE FLOW THROUGH THE PRIMARY SYSTEM SHALL NOT BE
 CONSIDERED WHEN LOCATING AND SIZING SECONDARY SCUPPERS.
 PER WPB FBC 107.2.1 PROVIDE CALCULATIONS IN COMPLIANCE
 WITH FBC PL 1106.5 AND FBC 1611.1.
  
 33. A2.3 ROOF PLAN NOTES SCUPPER LOCATION AND REFERS TO
 A8.4/DETAIL 9. THIS PLAN IS NOT PART OF THE DOCUMENTS.
 PER WPB FBC 107.2.1, PROVIDE THE PLAN OR PROVIDE DETAIL
 ON AN EXISTING PLAN.
  
 34. A2.3 AND P1.3 ROOF PLAN SHEETS SHOW SCUPPERS IN
 DIFFERENT LOCATIONS FROM EACH OTHER. PER WPB FBC
 107.2., CLARIFY AND RECONCILE.
  
  
 END OF COMMENTS.
  
 AN ATTEMPT HAS BEEN MADE TO MAKE THE MOST COMPREHENSIVE
 REVIEW POSSIBLE USING THE PLANS PROVIDED. A REVIEW OF
 RESUBMITTED PLANS MAY RESULT IN ADDITIONAL COMMENTS.
 PLEASE RESUBMIT CLEARLY LEGIBLE PLANS; A RESPONSE
 NARRATIVE ADDRESSING THE COMMENTS FROM THE PRIOR REVIEW
 WILL GREATLY HELP WITH THE REVIEW PROCESS AND IS VERY
 MUCH APPRECIATED.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21021445 3404 BROADWAY
  