Plan Review Notes
Plan Review Notes For Permit 21021445
Permit Number 21021445
Review Stop M
Sequence Number 1
Notes
Date Text
2021-04-21 08:17:161ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21021445
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE ALL CALCULATIONS AND CODE REFERENCES
 TO THE 2020 FBC M.
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS BASED ON WEST PALM BEACH, THE CALCULATIONS
 SUBMITTED ARE FOR THE MIAMI IAP. FBC EC C303
  
 3) PLEASE SHOW THAT THE DRYER DUCT TERMINATION LOCATION
 IS ON THE EXTERIOR OF THE BUILDING, NOT IN THE
 CORRIDOR. FBC M 504.4
  
 4) PLEASE SHOW THAT THE INTAKE OPENING FOR THE COFFEE
 BAR MEETS SECTION 401.4 (2).
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM)
 HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT
 SOURCE, SUCH AS VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS, EXCEPT AS SPECIFIED IN ITEM 3 OR
 SECTION 501.3.1.
  
 5) PLEASE PROVIDE A DETAIL DRAWING OF THE FIRST AND
 SECOND FLOOR BATH EXHAUST DUCTWORK, FROM FANS TO THE
 TERMINATION LOCATION. FBC 107.2.1
  
 6) PLEASE SHOW ACCESS FOR THE CONDENSING UNITS ON THE
 ROOF. FBC M 306.5
  
 7) PLEASE PROVIDE NOTES ON THE CONDENSATE DRAWING
 INDICATING THE PIPING MAINTAIN A MINIMUM HORIZONTAL
 SLOPE IN THE DIRECTION OF DISCHARGE OF NOT LESS THAN
 ONE-EIGHTH UNIT IN 12 UNITS HORIZONTAL (1 PERCENT
 SLOPE). FBC M 307.2.1
  
 8) PLEASE SHOW THE INLINE CHECK VALVE OR TRAP AT EACH
 FCU CONDENSATE LINE. FBC M 307.2.4.1
  
 9) PLEASE SHOW A DETAIL DRAWING OF HOW THE CONDENSATE
 DRAIN LINE SHALL BE CONFIGURED TO PERMIT THE CLEARING
 OF BLOCKAGES AND PERFORMANCE OF MAINTENANCE. FBC M
 307.2.5
  
 10) PLEASE INDICATE WHICH CIVIL SHEET AND THE DETAIL
 SHOWING THE LOCATION OF THE CONDENSATE DRAINAGE
 LOCATION AT THE EXTERIOR. FBC M 307.2.1
  
 11) PLEASE SHOW THE SECONDARY DRAIN OR SHOW THE WATER
 MONITORING DEVICE FOR EACH UNIT. FBC M 307.2.3.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  