| 2021-04-21 08:17:16 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021445 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE ALL CALCULATIONS AND CODE REFERENCES |
| | TO THE 2020 FBC M. |
| | |
| | 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS BASED ON WEST PALM BEACH, THE CALCULATIONS |
| | SUBMITTED ARE FOR THE MIAMI IAP. FBC EC C303 |
| | |
| | 3) PLEASE SHOW THAT THE DRYER DUCT TERMINATION LOCATION |
| | IS ON THE EXTERIOR OF THE BUILDING, NOT IN THE |
| | CORRIDOR. FBC M 504.4 |
| | |
| | 4) PLEASE SHOW THAT THE INTAKE OPENING FOR THE COFFEE |
| | BAR MEETS SECTION 401.4 (2). |
| | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) |
| | HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT |
| | SOURCE, SUCH AS VENTS, STREETS, ALLEYS, PARKING LOTS |
| | AND LOADING DOCKS, EXCEPT AS SPECIFIED IN ITEM 3 OR |
| | SECTION 501.3.1. |
| | |
| | 5) PLEASE PROVIDE A DETAIL DRAWING OF THE FIRST AND |
| | SECOND FLOOR BATH EXHAUST DUCTWORK, FROM FANS TO THE |
| | TERMINATION LOCATION. FBC 107.2.1 |
| | |
| | 6) PLEASE SHOW ACCESS FOR THE CONDENSING UNITS ON THE |
| | ROOF. FBC M 306.5 |
| | |
| | 7) PLEASE PROVIDE NOTES ON THE CONDENSATE DRAWING |
| | INDICATING THE PIPING MAINTAIN A MINIMUM HORIZONTAL |
| | SLOPE IN THE DIRECTION OF DISCHARGE OF NOT LESS THAN |
| | ONE-EIGHTH UNIT IN 12 UNITS HORIZONTAL (1 PERCENT |
| | SLOPE). FBC M 307.2.1 |
| | |
| | 8) PLEASE SHOW THE INLINE CHECK VALVE OR TRAP AT EACH |
| | FCU CONDENSATE LINE. FBC M 307.2.4.1 |
| | |
| | 9) PLEASE SHOW A DETAIL DRAWING OF HOW THE CONDENSATE |
| | DRAIN LINE SHALL BE CONFIGURED TO PERMIT THE CLEARING |
| | OF BLOCKAGES AND PERFORMANCE OF MAINTENANCE. FBC M |
| | 307.2.5 |
| | |
| | 10) PLEASE INDICATE WHICH CIVIL SHEET AND THE DETAIL |
| | SHOWING THE LOCATION OF THE CONDENSATE DRAINAGE |
| | LOCATION AT THE EXTERIOR. FBC M 307.2.1 |
| | |
| | 11) PLEASE SHOW THE SECONDARY DRAIN OR SHOW THE WATER |
| | MONITORING DEVICE FOR EACH UNIT. FBC M 307.2.3.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |