| 2021-04-23 11:56:11 | NEW 2 STORY APT. BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE NANAWALL |
| | DOOR. |
| | 2) ROOFING PRODUCT APPROVAL USING SYSTEM (W-69) WIND |
| | PRESSURE OF (-52.5) REQUIRES ADDITIONAL ATTACHMENT |
| | DETAILS FROM A DESIGN PROFESSIONAL PER NOTE 9 ON THE |
| | PRODUCT APPROVAL FOR WIND ZONES 2 (-80.93) AND WIND |
| | ZONE 3 (-113.92) PER DRAWING (S-5). |
| | 3) ROOFING PRODUCT APPROVAL FL5293 R39 IS EXPIRED |
| | PLEASE PROVIDE THE UPDATED VERSION FL5293 R44 AND THE |
| | UPDATED INSTALLATION INSTRUCTIONS. |
| | 4) PLEASE SHOW THE BOTTOM RAMP LANDING DIMENSIONS TO |
| | COMPLY WITH FBC A405.7 |
| | 5) THE OCCUPANCY CLASSIFICATION SHOWN ON THE COVER PAGE |
| | DRAWING SHOULD BE SHOWN AS MIXED R2 AND B. |
| | 6) PLEASE SHOW THAT THE DOOR SWING FROM THE LAUNDRY |
| | ROOM, ELEC. ROOM AND STORAGE ROOM DO NOT ENCROACH INTO |
| | THE MEANS OF EGRESS WITH PER FBC 1005.7.1 DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | 7) PLEASE SHOW THE HOURLY FIRE RATING BETWEEN UNITS AND |
| | BETWEEN UNITS AND BUSINESS OCCUPANCY TO COMPLY WITH FBC |
| | 420.2 - FBC 508.3.3 - FBC 708.3 |
| | 8) PLEASE SHOW THE HOURLY FIRE RATING FOR THE GLAZED |
| | SWING DOORS THAT OPEN INTO THE CORRIDORS TO COMPLY WITH |
| | FBC 716.1 FBC 1021.2 WALL SEPARATION. EXTERIOR EGRESS |
| | BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE |
| | BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED |
| | FOR CORRIDORS. (20 MIN. FIRE RATED GLASS WINDOWS AND |
| | DOORS FBC 716.1) |
| | 9) PLEASE PROVIDE A DETAIL SHOWING THE TOP OF THE UNIT |
| | SEPARATION WALL AND CORRIDOR WALL AT THE ROOF SHEATHING |
| | OF THE 2ND FLOOR. FBC 708.4 |
| | 10) PLEASE SHOW THE ATTIC VENTILATION TO COMPLY WITH |
| | FBC 1203.2 |
| | 11) PLEASE SHOW THE ACCESSIBLE RAMP HAND RAIL |
| | EXTENSIONS TO COMPLY WITH FBC A505.10.1 |
| | 12) PLEASE SHOW THE EXACT DIMENSION LOCATIONS FOR THE |
| | ACCESSIBLE BATH ROOM ACCESSORIES AND FIXTURES - REAR |
| | TOILET GRAB BAR FBC A604.5.2 - MIRROR TO THE REFLECTIVE |
| | SURFACE FBC A603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. - PAPER HOLDER FBC A604.7 |
| | DISPENSERS.TOILET PAPER DISPENSERS SHALL COMPLY WITH |
| | 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 |
| | INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM |
| | AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR |
| | AND SHALL NOT BE LOCATED BEHIND GRAB BARS. ETC.. |
| | 13) PLEASE SHOW THE DOOR MANEUVERING SPACE FROM THE |
| | INSIDE OF THE RESTROOM IN THE COFFEE SHOP TO COMPLY |
| | WITH FBC A404.2.4.1 |
| | 14) PLEASE SHOW THE CHECK OUT COUNTER HEIGHT TO COMPLY |
| | WITH FBC A904 |
| | 15) PLEASE SHOW THE COFFEE COUNTER IN THE COFFEE SHOP |
| | TO COMPLY WITH FBC A904. |
| | 16) PLEASE SHOW THE BARRIER UNDER THE PROTRUDING STAIR |
| | TO COMPLY WITH FBC A307.4 |
| | 17) PLEASE SHOW THE COFFEE SHOP RESTROOM WALL FINISHES |
| | TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | 18) PLEASE SHOW THE LAUNDRY ROOM TO BE ACCESSIBLE PER |
| | FBC A FAIR HOUSING SECTION 5 REQUIREMENT NUMBER 2 (SHOW |
| | THE CLEAR FLOOR SPACE). |
| | 19 ) PLEASE SHOW THE UNIT SEPARATION WALLS STC RATING |
| | TO COMPLY WITH FBC 1207.2 AIRBORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90 |
| | 20) FOR THE HARD SURFACE FLOORING - THE FOLLOWING |
| | ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | 21) SEPARATE PERMITS ARE REQUIRED FOR - SITE WALLS, |
| | STRIPING OF PARKING, RETAINING WALLS, CONSTRUCTION |
| | TRAILER, FENCE, DUMPSTER ENCLOSURE, BUILDING DEMO. |
| | PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS. |
| | 22) PLEASE RECONSIDER THE LOCATION OF THE ACCESSIBLE |
| | PARKING SPACE TO COMPLY WITH FBC 208.3.1 PARKING SPACES |
| | COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR |
| | FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE |
| | ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4. |
| | - PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE |
| | PARKING TO THE COFFEE SHOP. ALL SPACES MUST BE LOCATED |
| | ON AN ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES (1118 |
| | MM) WIDE AND SO THAT USERS ARE NOT COMPELLED TO WALK OR |
| | WHEEL BEHIND PARKED VEHICLES EXCEPT BEHIND HIS OR HER |
| | OWN VEHICLE.FBC 208.3.1 |
| | 23) PLEASE SHOW THE SQUARE FOOTAGE FOR EACH UNIT - |
| | PLEASE SHOW THE SQUARE FOOTAGE FOR THE CORRIDORS - |
| | PLEASE SHOW THE SQUARE FOOTAGE FOR THE COFFEE SHOP. |
| | COVER SHEET DOES NOT SHOW ALL SQUARE FOOTAGE CORRECTLY. |
| | |
| | |