Plan Review Notes
Plan Review Notes For Permit 21021445
Permit Number 21021445
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-23 11:56:11NEW 2 STORY APT. BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE NANAWALL
 DOOR.
 2) ROOFING PRODUCT APPROVAL USING SYSTEM (W-69) WIND
 PRESSURE OF (-52.5) REQUIRES ADDITIONAL ATTACHMENT
 DETAILS FROM A DESIGN PROFESSIONAL PER NOTE 9 ON THE
 PRODUCT APPROVAL FOR WIND ZONES 2 (-80.93) AND WIND
 ZONE 3 (-113.92) PER DRAWING (S-5).
 3) ROOFING PRODUCT APPROVAL FL5293 R39 IS EXPIRED
 PLEASE PROVIDE THE UPDATED VERSION FL5293 R44 AND THE
 UPDATED INSTALLATION INSTRUCTIONS.
 4) PLEASE SHOW THE BOTTOM RAMP LANDING DIMENSIONS TO
 COMPLY WITH FBC A405.7
 5) THE OCCUPANCY CLASSIFICATION SHOWN ON THE COVER PAGE
 DRAWING SHOULD BE SHOWN AS MIXED R2 AND B.
 6) PLEASE SHOW THAT THE DOOR SWING FROM THE LAUNDRY
 ROOM, ELEC. ROOM AND STORAGE ROOM DO NOT ENCROACH INTO
 THE MEANS OF EGRESS WITH PER FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 7) PLEASE SHOW THE HOURLY FIRE RATING BETWEEN UNITS AND
 BETWEEN UNITS AND BUSINESS OCCUPANCY TO COMPLY WITH FBC
 420.2 - FBC 508.3.3 - FBC 708.3
 8) PLEASE SHOW THE HOURLY FIRE RATING FOR THE GLAZED
 SWING DOORS THAT OPEN INTO THE CORRIDORS TO COMPLY WITH
 FBC 716.1 FBC 1021.2 WALL SEPARATION. EXTERIOR EGRESS
 BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED
 FOR CORRIDORS. (20 MIN. FIRE RATED GLASS WINDOWS AND
 DOORS FBC 716.1)
 9) PLEASE PROVIDE A DETAIL SHOWING THE TOP OF THE UNIT
 SEPARATION WALL AND CORRIDOR WALL AT THE ROOF SHEATHING
 OF THE 2ND FLOOR. FBC 708.4
 10) PLEASE SHOW THE ATTIC VENTILATION TO COMPLY WITH
 FBC 1203.2
 11) PLEASE SHOW THE ACCESSIBLE RAMP HAND RAIL
 EXTENSIONS TO COMPLY WITH FBC A505.10.1
 12) PLEASE SHOW THE EXACT DIMENSION LOCATIONS FOR THE
 ACCESSIBLE BATH ROOM ACCESSORIES AND FIXTURES - REAR
 TOILET GRAB BAR FBC A604.5.2 - MIRROR TO THE REFLECTIVE
 SURFACE FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. - PAPER HOLDER FBC A604.7
 DISPENSERS.TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
 AND SHALL NOT BE LOCATED BEHIND GRAB BARS. ETC..
 13) PLEASE SHOW THE DOOR MANEUVERING SPACE FROM THE
 INSIDE OF THE RESTROOM IN THE COFFEE SHOP TO COMPLY
 WITH FBC A404.2.4.1
 14) PLEASE SHOW THE CHECK OUT COUNTER HEIGHT TO COMPLY
 WITH FBC A904
 15) PLEASE SHOW THE COFFEE COUNTER IN THE COFFEE SHOP
 TO COMPLY WITH FBC A904.
 16) PLEASE SHOW THE BARRIER UNDER THE PROTRUDING STAIR
 TO COMPLY WITH FBC A307.4
 17) PLEASE SHOW THE COFFEE SHOP RESTROOM WALL FINISHES
 TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
 18) PLEASE SHOW THE LAUNDRY ROOM TO BE ACCESSIBLE PER
 FBC A FAIR HOUSING SECTION 5 REQUIREMENT NUMBER 2 (SHOW
 THE CLEAR FLOOR SPACE).
 19 ) PLEASE SHOW THE UNIT SEPARATION WALLS STC RATING
 TO COMPLY WITH FBC 1207.2 AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90
 20) FOR THE HARD SURFACE FLOORING - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 21) SEPARATE PERMITS ARE REQUIRED FOR - SITE WALLS,
 STRIPING OF PARKING, RETAINING WALLS, CONSTRUCTION
 TRAILER, FENCE, DUMPSTER ENCLOSURE, BUILDING DEMO.
 PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS.
 22) PLEASE RECONSIDER THE LOCATION OF THE ACCESSIBLE
 PARKING SPACE TO COMPLY WITH FBC 208.3.1 PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4.
 - PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING TO THE COFFEE SHOP. ALL SPACES MUST BE LOCATED
 ON AN ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES (1118
 MM) WIDE AND SO THAT USERS ARE NOT COMPELLED TO WALK OR
 WHEEL BEHIND PARKED VEHICLES EXCEPT BEHIND HIS OR HER
 OWN VEHICLE.FBC 208.3.1
 23) PLEASE SHOW THE SQUARE FOOTAGE FOR EACH UNIT -
 PLEASE SHOW THE SQUARE FOOTAGE FOR THE CORRIDORS -
 PLEASE SHOW THE SQUARE FOOTAGE FOR THE COFFEE SHOP.
 COVER SHEET DOES NOT SHOW ALL SQUARE FOOTAGE CORRECTLY.
  
  