| Plan Review Notes For Permit 21021430 |
| Permit Number |
21021430 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-11-02 12:36:15 | 4TH REVIEW FMC | | | PERMIT: 21021430 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALLS FOR 1.24 | | | NOMINAL TONS OF SENSIBLE COOLING. SHEET M-1 IN THE | | | MECHANICAL SCHEDULE CALLS FOR A 2-TON SYSTEM. PLEASE | | | SHOW HOW THIS MEETS THE REQUIREMENTS OF FEC | | | R403.7.1.2.2 BELOW: | | | | | | R403.7.1.2.1 HEAT PUMPS. HEAT PUMP SIZING SHALL BE | | | BASED ON THE COOLING REQUIREMENTS AS CALCULATED | | | ACCORDING TO SECTION R403.7.1.1, AND THE HEAT PUMP | | | TOTAL COOLING CAPACITY SHALL NOT BE MORE THAN 1.15 | | | TIMES GREATER THAN THE DESIGN COOLING LOAD EVEN IF THE | | | DESIGN HEATING LOAD IS 1.15 TIMES GREATER THAN THE | | | DESIGN COOLING LOAD. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|