| 2022-11-01 14:58:15 | ELECTRIC REVIEW FAILED |
| | 1) IT APPEARS GUEST COTTAGE DETAILS MORE THAN ONE MULTI |
| | WIRE CIRCUIT. PLEASE INDICATE THAT GUEST HOUSE HAS |
| | SUBPANEL FOR GUEST HOUSE LOADS. AS PER NEC 225.30 |
| | IN ADDITION, SINCE THIS GUEST HOUSE APPEARS IT WILL |
| | REQUIRE AN ELECTRIC SUB PANEL, INDICATE THE NECESSARY |
| | GROUNDING ELECTRODE SYSTEM AS PER NEC 250.32 |
| | 2) PROVIDE AN ELECTRICAL RISER DIAGRAM DETAILING ALL |
| | ELECTRIC EQIPMENT, METERS PANELS, CONDUIT ANND |
| | CONDUCTOR SIZES AS NEC 215.5 |
| | 3) PLEASE PROVIDE LOAD CALCULATIONS FOR ALL |
| | DISTRIBUTION PANELS NEC 220 |
| | 4) PLEASE LOCATE ALL ELECTRIC EQUIPMENT ON A SITE PLAN |
| | FBC 107.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |