| 2022-02-16 15:09:21 | THE HVAC LOAD CALCULATIONS AND THE MECHANICAL DRAWING | | | DO NOT MATCH. PLEASE SUBMIT DOCUMENTS THAT MATCH EACH | | | OTHER. THE LOAD CALCULATIONS MENTION HYDRONIC BASEBOARD | | | HEAT BUT THERE IS NOTHING ON THE MECHANICAL DRAWING | | | ABOUT THIS. THE LOAD CALCULATIONS SHOW 11979 BTUH BUT | | | THE MECHANICAL DRAWING SHOWS A 2-TON UNIT. THE LOAD | | | CALCULATIONS SHOW THAT A ZONED SYSTEM MUST BE INSTALLED | | | BECAUSE OF THE LARGE SPIKES IN SOLAR LOAD BUT THE | | | DRAWING SHOWS A 1 ROOM STRUCTURE WITHOUT A ZONED | | | SYSTEM. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|