| 2021-10-18 12:36:16 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021430 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW |
| | STRUCTURE AS REQUESTED IN THE FIRST REVIEW COMMENTS. |
| | FBC EC 101.5.1.1.2 |
| | |
| | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS AS REQUESTED IN THE FIRST REVIEW COMMENTS. |
| | FBC EC R403.7.1 |
| | |
| | 3) SHEET M-1 SHOWS A MINI-SPLIT ONLY AND ONLY A FIRST |
| | FLOOR. S1-3 INDICATES DUCTWORK FOR THE FIRST AND SECOND |
| | FLOOR BUT DOES NOT SHOW THE MECHANICAL SYSTEM. PLEASE |
| | PROVIDE MECHANICAL DRAWINGS THAT ARE CONSISTENT AND |
| | PROVIDE DETAILS FOR THE MECHANICAL SYSTEM. INCLUDING |
| | THE LOCATION OF THE AHU AND THE CONDENSING UNIT ALONG |
| | WITH THE ANCHORING DETAILS OF THE CONDENSING UNIT. |
| | PLEASE ALSO SHOW THE CONDENSATE PIPING AND TERMINATION |
| | LOCATION. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |