| 2021-03-25 12:11:55 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021430 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL |
| | SYSTEM INSTALLATION. IS THERE GOING TO BE A NEW |
| | MECHANICAL SYSTEM INSTALLED OR IS THE MECHANICAL DESIGN |
| | USING THE EXISTING SYSTEM TO CONDITION THIS NEW |
| | STRUCTURE? FBC 107.2.1 |
| | |
| | 2) MECHANICAL ENGINEER OR MECHANICAL CONTRACTOR THAT IS |
| | CONTRACTED TO INSTALL THE MECHANICAL SYSTEM MUST SUBMIT |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS |
| | PROJECT. FBC EC R403.7.1 |
| | |
| | 3) THE DESIGNER OF THE MECHANICAL DRAWING MUST SHOW THE |
| | BATH EXHAUST. FBC RES M1507.4 |
| | |
| | 4) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW |
| | CONSTRUCTION. FBC EC 101.5.1.1.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |