| 2021-03-05 10:38:02 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021410 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) PLEASE CLARIFY WORK DESCRIPTION ON THE PERMIT |
| | APPLICATION. ? INSTALL HOOD SYSTEM AND KITCHEN COOL? |
| | WHAT IS THE KITCHEN COOL? THIS SHOULD BE A HOOD SYSTEM |
| | ONLY PERMIT. |
| | |
| | 2) THE AMOUNT OF MAKE UP AIR SUPPLIED TO THE BUILDING |
| | FROM ALL SOURCES SHALL BE APPROXIMATELY EQUAL TO THE |
| | AMOUNT OF EXHAUST AIR FOR ALL EXHAUST SYSTEMS FOR THE |
| | BUILDING. PLEASE SHOW ALL EXHAUST SUCH AS BATH EXHAUST |
| | IN THE AIR BALANCE REPORT. PLEASE EXPLAIN HOW THE |
| | BUILDING HVAC SYSTEM IS TO PROVIDE MORE THAN 650 CFM |
| | WHEN THE KITCHEN DOES NOT HAVE A MECHANICAL SYSTEM FOR |
| | CONDITIONING THE AREA. FBC M 508.1.1, FBC M 508.1.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |