| 2021-03-25 14:52:59 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021394 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A COMPLETE SCOPE OF WORK, HOW MANY |
| | UNITS WILL BE CHANGED OUT? FBC 107.2.1 |
| | |
| | 2) PLEASE PROVIDE THE ?LIKE FOR LIKE? CHANGEOUT FORMS |
| | FOR EACH UNIT BEING CHANGED OUT. FBC 107.2.1 |
| | |
| | 3) THE SHEET A1.3 IS A COPY OF AN ORIGINAL DRAWING AND |
| | IS UNREADABLE. PLEASE PROVIDE A READABLE DRAWING. FBC |
| | 107.2.1 |
| | |
| | 4) THE VALUE GIVEN ON THE PERMIT APPLICATION SEEMS TO |
| | BE LOW, PLEASE INCLUDE A CONTRACT FOR THIS PROJECT. FBC |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |