| 2021-03-18 16:44:43 | 03/18/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. ON PAGE A-1L; |
| | A. IT SHOWS A GAS TANK-LESS. PLEASE PROVIDE A NOTE ON |
| | PLANS THAT A SEPARATE PERMIT SHALL BE SUBMITTED FOR GAS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | B. THE TANKLESS HOT WATER LINES ON THE OUTSIDE SHALL |
| | HAVE INSULATED MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| | 403.5.3. PLEASE PLACE A NOTE. |
| | |
| | C. IF THIS HAS A CONDENSATE, IT WILL NEED TO BE 1' AWAY |
| | FROM THE STRUCTURE PER THE 2017 FBC SEC. R318.5. |
| | |
| | D. PLEASE SHOW THE TANK-LESS WATER HEATER'S LOCATION |
| | AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| | OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | |
| | 3. ON SHEET S1L AND S1R; |
| | A. THE LINE SANITARY LINE ON THE ISOMETRIC OF THE |
| | MASTER THAT GOES TO PICK UP THE LAVS AND SHOWER IS |
| | SHOWN AND PLACED IN THE WRONG DIRECTION. SEE SHEETS FOR |
| | REDLINE CORRECTION. |
| | |
| | B. THE WASHING MACHINE LINE IS TWO-INCH, PER MOST |
| | MANUFACTURES' SPECIFICATIONS, A 3" LINE IS SPECIFIED |
| | AND PLEASE SHOW WASHER BOX. PLEASE CHANGE OR PROVIDE |
| | THE SPECIFICATION FOR THE WASHING MACHINE THAT SAYS |
| | OTHERWISE. |
| | |
| | PLEASE CORRECT THESE ITEMS PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |