| 2021-04-30 09:30:42 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021356 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SEE BUILDING REVIEWER COMMENTS. |
| | |
| | 2) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS |
| | GENERATOR INSTALLATION. |
| | |
| | 3) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN |
| | THE GENERATOR ROOM. PLEASE INCLUDE THE EXHAUST DETAILS |
| | OF THE GENERATOR INCLUDING LOCATION OF THE TERMINATION |
| | AND HEIGHT IT IS EXITING THE BUILDING. FBC 107.2.1; FBC |
| | M 607 |
| | |
| | 4) PLEASE SHOW THE PROPERTY LINES AND DISTANCE AWAY |
| | FROM PROPERTY LINES FOR THE GENERATOR EXHAUST. FBC M |
| | 501.3.1 |
| | |
| | 5) PLEASE SHOW THE METHOD OF TANK FILL FOR THE DIESEL |
| | FUEL TANK. FBC M 1305.6 |
| | |
| | 6) PLEASE PROVIDE A DETAIL FUEL PIPING DRAWING |
| | INDICATING THE PIPING TYPE AND SIZES. FBC M 1305 |
| | |
| | 7) PLEASE SOW THE VENT PIPING FOR THE TANK AND THE |
| | TERMINATION LOCATION. FBC M 1305.7 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |