| Date |
Text |
| 2022-08-03 15:59:38 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 21021355- STANDBY GENERATOR |
| | 8/3/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | NFPA 37, 54 & 110 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS. |
| | |
| | 3) FAILED. CORRECT SHEET E-407 SHOWING GENERATOR SPECS |
| | FOR MTU 4R0063 GS30. THE APPROVED SUBMITTAL UPLOADED IS |
| | FOR A CUMMINGS C30 NG- SECTION 107.2.1 WPB AND SECTION |
| | 305.1 FBC FG. CORRECTION NOT PROVIDED. |
| | |
| | 7) FAILED. INDICATE HOW COMBUSTION AIR WILL BE PROVIDED |
| | TO THE GENERATOR AND PROVIDE CALCULATIONS- SECTION |
| | 304.1 FBC FG. A) SHEET M103: THE COMBUSTION AIR |
| | CALCULATIONS SHOW THEY ARE BASED ON 38,500 BTU/HR LOAD |
| | HOWEVER THE GENERATOR SPECS INDICATE 389,000 BTU/HR. |
| | PLEASE CORRECT. B) M103: PLEASE LABEL THE SUPPLY CFMS |
| | AT THE DIFFUSER IN THE GENERATOR ROOM. |
| | |
| | NEW COMMENTS BASED ON RESUBMITTED PLANS. |
| | |
| | 1) SHEETS P-101B, P-242, & P-505: THE UPDATED PLAN |
| | SHEETS DO NOT MATCH. |
| | |
| | A) SHEET P-101B SHOWS ONLY ONE METER AND THE PIPE RUNS |
| | AND PIPE SIZES DO NOT MATCH THE ENLARGED PIPING LAYOUT |
| | DRAWING (P-242) AND THE RISER (P-505. |
| | |
| | B) P-242 SHOWS A 2-1/2 LOW PRESSURE SUPPLY LINE ON |
| | LEVEL 01 FROM THE METER TO THE VERTICAL RISER PIPE, |
| | HOWEVER THE ISOMETRIC DRAWING (P-505) SHOWS A 3-INCH |
| | PIPE. WHICH IS IT? |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |
| | |
| | |