| 2021-04-30 08:37:50 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021355 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS |
| | GENERATOR INSTALLATION. |
| | |
| | 2) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN |
| | THE GENERATOR ROOM. PLEASE IDENTIFY THE INTAKE AIR |
| | LOCATION AND INCLUDE THE EXHAUST DETAILS OF THE |
| | GENERATOR. THE ORIGINAL APPROVED DRAWINGS DO NOT SHOW |
| | THE GENERATOR ROOM INSIDE OF THE MECHANICAL ROOM. THERE |
| | IS ELEVATOR PRESSURIZATION DUCT WORK FOR OUTDOOR AIR |
| | LOCATED INSIDE OF THIS ROOM. IF THE NEW WALLS FOR THE |
| | GENERATOR ROOM ARE REQUIRED TO BE FIRE RATED PLEASE |
| | REVISE THE APPROVED DRAWING SHOWING THE RATED WALLS AND |
| | THE PROTECTION REQUIRED FOR THE ELEVATOR PRESSURIZATION |
| | DUCTWORK. FBC 107.2.1; FBC M 607 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |