| 2021-04-29 09:29:15 | 3RD FLOOR GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A DRAWING THAT SHOWS THE PATH OF THE | | | GAS LINE TO COMPLY WITH FBC 403.4.8.2 FUEL LINE PIPING | | | PROTECTION. | | | FUEL LINES SUPPLYING A GENERATOR SET INSIDE A BUILDING | | | SHALL BE SEPARATED FROM AREAS OF THE BUILDING OTHER | | | THAN THE ROOM THE GENERATOR IS LOCATED IN BY AN | | | APPROVED METHOD OR ASSEMBLY THAT HAS A FIRE-RESISTANCE | | | RATING OF NOT LESS THAN 2 HOURS. WHERE THE BUILDING IS | | | PROTECTED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM | | | INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR | | | 903.3.1.2, THE REQUIRED FIRE-RESISTANCE RATING SHALL BE | | | REDUCED TO 1 HOUR. |
|