| 2021-03-17 10:34:50 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21021343 |
| | 3/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COVER SHEET: THE PLUMBING FIXTURE CALCULATIONS DO |
| | NOT INCLUDE THE STORAGE OCCUPANCY CALCULATIONS- TABLE |
| | 403.1 FBC P. |
| | |
| | 2) A1: PLEASE LABEL THE TOILET ROOMS AS EITHER MALE OR |
| | FEMALE ACCORDING TO TABLE 403.1 AND 403.2 FBC P. |
| | |
| | 3) SHEET A-2: SHOW THE HEIGHTS OF THE GRAB BARS FROM |
| | THE FINISHED FLOORS TO THE TOPS OF THE GRIPPING |
| | SURFACES- - SECTION 609.4 FBC ACC. |
| | |
| | 4) A-2: THE REAR GRAB BEHIND THE WATER CLOSET MUST BE |
| | CENTERED ACCORDING TO SECTION AND FIGURE 604.5.2 FBC |
| | ACC. |
| | |
| | 5) A-2: RELOCATE THE WATER CLOSET FLUSH CONTROL TO THE |
| | OPEN SIDE OF THE WATER CLOSET- SECTION 604.6 FBC ACC. |
| | |
| | 6) P1: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING |
| | MAKES, MODELS AND COMPLIANCE STANDARDS- SECTIONS 419, |
| | 422, AND 425 FBC P. |
| | |
| | 7) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | CHRONOMITE WATER HEATER VERIFYING THE UNIT IS ASSE 1070 |
| | LISTED TO PROVIDE TEMPERED WATER TO THE LAVATORIES. IF |
| | THE UNIT IS NOT ASSE 1070 APPROVED PLEASE PROVIDE A |
| | MIXING VALVE IN ACCORDANCE WITH SECTION 607.1.2 FBC P. |
| | |
| | 8) P1: THE WATER RISER SHOWS A COLD WATER LINE TO THE |
| | EXISTING MOP SINK, HOWEVER HOT WATER IS REQUIRED PER |
| | SECTION 607.1 FBC P. PLEASE SHOW THE SOURCE OF THE HOT |
| | WATER. |
| | |
| | 9) P1: PLEASE REMOVE THE WORD ASSUMED FROM THE SANITARY |
| | RISER AND PROVIDE COMPLETE WET VENTING DETAILS FOR THE |
| | NEW ADA TOILET ROOM- SECTION 912.1 FBC P. |
| | |
| | 10) P1: SHOW IN THE SANITARY RISER THERE IS AN EXISTING |
| | VENT TO THE OUTDOORS SERVING THE BUILDING DRAIN AS |
| | REQUIRED BY SECTION 904.1 FBC P. |
| | |
| | 11) P1: THE NOTE AT BOTTOM LEFT OF THE SHEET CALLS OUT |
| | TRAP PRIMER VALVE FOR FLOOR DRAIN, HOWEVER NO FLOOR |
| | DRAIN IS SHOWN IN THE DRAWINGS- PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |