| 2021-03-16 11:02:07 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021343 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE ARE DEHUMIDIFYING UNITS AVAILABLE FOR |
| | COMMERCIAL WAREHOUSES, IF THIS IS THE INTENT PLEASE |
| | SUBMIT SPECIFICATIONS AND CALCULATIONS FOR THIS USE. IF |
| | USING A RTU THEN YOU MUST SUBMIT ENERGY CALCULATIONS |
| | ALONG WITH THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC C101.4.2.4 (5) FBC EC C402; FBC M |
| | 312.1 I CANNOT COMPLETE THE REVIEW UNTIL THIS COMMENT |
| | HAS BEEN ADDRESSED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |