2021-03-15 16:57:44PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THIS APPLICATION IS FOR A ROOF OVER.
  
 1. SUBMIT ANALYSIS REPORT OF EXISTING ROOF BY A DESIGN
 PROFESSIONAL.
 R908.3 RECOVERING VERSUS REPLACEMENT.
 NEW ROOF COVERINGS SHALL NOT BE INSTALLED WITHOUT FIRST
 REMOVING ALL EXISTING LAYERS OF ROOF COVERINGS WHERE
 ANY OF THE FOLLOWING CONDITIONS OCCUR:
 1.WHERE THE EXISTING ROOF OR ROOF COVERING IS WATER
 SOAKED OR HAS DETERIORATED TO THE POINT THAT THE
 EXISTING ROOF OR ROOF COVERING IS NOT ADEQUATE AS A
 BASE FOR ADDITIONAL ROOFING.
 2.WHERE THE EXISTING ROOF COVERING IS WOOD SHINGLE OR
 SHAKE, SLATE, CLAY, CEMENT OR ASBESTOS-CEMENT TILE.
 3.WHERE THE EXISTING ROOF HAS TWO OR MORE APPLICATIONS
 OF ANY TYPE OF ROOF COVERING.
 4.WHEN BLISTERS EXIST IN ANY ROOFING, UNLESS BLISTERS
 ARE CUT OR SCRAPED OPEN AND REMAINING MATERIALS SECURED
 DOWN BEFORE APPLYING ADDITIONAL ROOFING.
 5.WHERE THE EXISTING ROOF IS TO BE USED FOR ATTACHMENT
 FOR A NEW ROOF SYSTEM AND COMPLIANCE WITH THE
 SECUREMENT PROVISIONS OF SECTION R905 CANNOT BE MET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  