| Plan Review Notes For Permit 21021340 |
| Permit Number |
21021340 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-10 14:56:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SUBMIT A LOAD CALCULATION FOR THE ADDITIONAL | | | LOADS TO THE SERVICE. | | | | | | SUBMIT A RISER DIAGRAM, AND PANEL SCHEDULE. |
|