| Plan Review Notes For Permit 21021340 |
| Permit Number |
21021340 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-18 15:47:45 | ENCLOSE CARPORT TO LIVING SPACE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE WATER RESISTIVE BARRIER TO COMPLY | | | WITH FBC R703.2 WATER-RESISTIVE BARRIER. | | | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND | | | BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR | | | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED | | | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. | | | 2) DESIGN WIND SPEED SHOULD BE SHOWN AS ( VULT170MPH ) | | | PER FBC WPB 120. | | | 3) PLEASE SHOW THE WALL AND CEILING INSULATION ON THE | | | DRAWINGS TO MATCH THE ENERGY CALCS. (R 19 IN A 2X6 WALL | | | WILL BE COMPRESSED AND NOT GIVE YOU R19 VALUE). | | | 4) PLEASE SHOW THE CEILING HEIGHT TO COMPLY WITH FBC | | | R305.1 | | | 5) PLEASE SHOW THE REQUIRED SMOKE ALARMS THROUGHOUT THE | | | EXISTING HOUSE TO COMPLY WITH FBC R314.2.2 ALTERATIONS, | | | REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | |
|