| Date |
Text |
| 2021-03-09 11:49:36 | 03/09/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | THESE COMMENTS BELOW ARE NOT FOR THE ENGINEER AND CAN |
| | BE ADDRESSED BY THE GENERAL CONTRACTOR. SOME REDLINE |
| | WILL BE DONE ON PLANS BY YOURS TRULY FOR THE GAS |
| | PORTION. |
| | |
| | 1. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS(GENERATOR AND |
| | TANKLESS) EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC |
| | RES. SEC. G 305.1. |
| | |
| | 2. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE FBC RES. SEC. G 410.1. |
| | |
| | 3. REDLINE, PIPES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. CE |
| | 404.4. |
| | |
| | 4. REDLINE, IF THE TANKLESS HAS A CONDENSATE, IT WILL |
| | NEED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC |
| | SEC. R318.5. |
| | |
| | 5. REDLINE, SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2017 FBC FG SEC 410.2. |
| | |
| | 6. REDLINE, LABEL THE SHUTOFF VALVE UNION ON GAS |
| | ISOMERIC PER THE 2017 FBC FG SEC. 409.4. |
| | |
| | 7. A LICENSED CONTRACTOR HAS APPLIED FOR A GAS PERMIT |
| | FOR THE SCOPE OF WORK. IT HAS COMMENTS THAT HAVE NOT |
| | BEEN ADDRESSED BUT ARE IN THIS REVISION. PLEASE MAKE |
| | THE GAS A SUB PERMIT AND REFER IT TO THIS AS A MASTER |
| | AND LAPEL; PER PLANS, PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1. |
| | |
| | 8. AN ELECTRICAL PERMIT IS REQUIRED FOR THE GENERATOR |
| | BY A LICENSED CONTRACTOR PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |