2021-03-09 11:49:3603/09/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THESE COMMENTS BELOW ARE NOT FOR THE ENGINEER AND CAN
 BE ADDRESSED BY THE GENERAL CONTRACTOR. SOME REDLINE
 WILL BE DONE ON PLANS BY YOURS TRULY FOR THE GAS
 PORTION.
  
 1. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS(GENERATOR AND
 TANKLESS) EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC
 RES. SEC. G 305.1.
  
 2. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE FBC RES. SEC. G 410.1.
  
 3. REDLINE, PIPES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. CE
 404.4.
  
 4. REDLINE, IF THE TANKLESS HAS A CONDENSATE, IT WILL
 NEED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC
 SEC. R318.5.
  
 5. REDLINE, SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
  
 6. REDLINE, LABEL THE SHUTOFF VALVE UNION ON GAS
 ISOMERIC PER THE 2017 FBC FG SEC. 409.4.
  
 7. A LICENSED CONTRACTOR HAS APPLIED FOR A GAS PERMIT
 FOR THE SCOPE OF WORK. IT HAS COMMENTS THAT HAVE NOT
 BEEN ADDRESSED BUT ARE IN THIS REVISION. PLEASE MAKE
 THE GAS A SUB PERMIT AND REFER IT TO THIS AS A MASTER
 AND LAPEL; PER PLANS, PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 8. AN ELECTRICAL PERMIT IS REQUIRED FOR THE GENERATOR
 BY A LICENSED CONTRACTOR PER THE WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  