Plan Review Notes
Plan Review Notes For Permit 21021295
Permit Number 21021295
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-04 09:49:511) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/DRYER
 SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING
 SEC.606.3.
 2) THE PLANS REFER TO THE USE OF AIR ADMITTANCE VALVES
 ON SOME OF THE PLUMBING FIXTURES. THE AIR ADMITTANCE
 VALVE IS NOT PERMITTED TO BE USED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK UNLESS A RELIEF
 VENT IS INSTALLED IN ACCORDANCE WIH FBC-PLUMBING
 SEC.918.3.1.
 3) SUBMIT FIRESTOPPING DETAILS FOR ANY NEW PLUMBING
 PENETRATIONS THAT WILL BE MADE THROGH THE EXISTING
 SLAB.WPB AMEND. TO FBC SEC. 107.3.5.1.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW