| Notes |
| Date |
Text |
| 2021-05-04 09:49:51 | 1) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/DRYER | | | SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING | | | SEC.606.3. | | | 2) THE PLANS REFER TO THE USE OF AIR ADMITTANCE VALVES | | | ON SOME OF THE PLUMBING FIXTURES. THE AIR ADMITTANCE | | | VALVE IS NOT PERMITTED TO BE USED MORE THAN FOUR BRANCH | | | INTERVALS FROM THE TOP OF THE STACK UNLESS A RELIEF | | | VENT IS INSTALLED IN ACCORDANCE WIH FBC-PLUMBING | | | SEC.918.3.1. | | | 3) SUBMIT FIRESTOPPING DETAILS FOR ANY NEW PLUMBING | | | PENETRATIONS THAT WILL BE MADE THROGH THE EXISTING | | | SLAB.WPB AMEND. TO FBC SEC. 107.3.5.1.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|