2021-03-15 06:26:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21021282
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS A LESS THAN 2 PSI SYSTEM WITH A TOTAL
 DEVELOPED LENGTH OF 90 FEET. WITHOUT ANY OTHER
 INFORMATION ABOUT THE TYPE OF SYSTEM I MUST ASSUME THAT
 THE DESIGNER IS USING THE LONGEST LENGTH METHOD FOR
 SIZING THIS SYSTEM. BASED ON THE REFERENCED TABLE AT 90
 FEET FOR THE NEW RANGE THE ?? PIPE IS UNDERSIZED. BASED
 ON THE SAME TABLE THE NEW TOTAL LOAD HAS INCREASED SO
 THE 1? PIPE FROM THE METER TO THE FIRST T FITTING IS
 ALSO UNDERSIZED. AS THE BTU?S FOR THE EXISTING WATER
 HEATER AND DRYER ARE NOT GIVEN AND THE PIPE SIZING FOR
 THIS BRANCH IS NOT GIVEN I CANNOT SIZE THIS EXISTING
 BRANCH WITH THE NEW TOTAL DEVELOPED LENGTH.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  