| 2021-03-15 06:26:42 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021282 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS A LESS THAN 2 PSI SYSTEM WITH A TOTAL |
| | DEVELOPED LENGTH OF 90 FEET. WITHOUT ANY OTHER |
| | INFORMATION ABOUT THE TYPE OF SYSTEM I MUST ASSUME THAT |
| | THE DESIGNER IS USING THE LONGEST LENGTH METHOD FOR |
| | SIZING THIS SYSTEM. BASED ON THE REFERENCED TABLE AT 90 |
| | FEET FOR THE NEW RANGE THE ?? PIPE IS UNDERSIZED. BASED |
| | ON THE SAME TABLE THE NEW TOTAL LOAD HAS INCREASED SO |
| | THE 1? PIPE FROM THE METER TO THE FIRST T FITTING IS |
| | ALSO UNDERSIZED. AS THE BTU?S FOR THE EXISTING WATER |
| | HEATER AND DRYER ARE NOT GIVEN AND THE PIPE SIZING FOR |
| | THIS BRANCH IS NOT GIVEN I CANNOT SIZE THIS EXISTING |
| | BRANCH WITH THE NEW TOTAL DEVELOPED LENGTH. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |