| Date |
Text |
| 2021-03-05 15:29:54 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21021282 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P0.1: ON THE GAS ISOMETRIC I SEE THAT THE |
| | REGULATOR HAS BEEN REMOVED FROM THE AREA AT THE GAS |
| | METER. THIS MAKES THIS APPEARS TO MAKE THE ENTIRE |
| | SYSTEM A 2 PSI SYSTEM. WAS THE EXISTING SYSTEM A 2 PSI |
| | SYSTEM? I DO NOT SEE ANY REGULATORS TO DROP THE |
| | PRESSURE BEFORE THE EXISTING APPLIANCES. THE GAS TABLE |
| | USED FOR SIZING THIS SYSTEM IS STILL SHOWN TO BE T. |
| | 402.4(2) WHICH IS A LESS THAN 2 PSI TABLE. PLEASE |
| | RECHECK THE ENTIRE SYSTEM AND PROVIDE A COMPLETE CODE |
| | COMPLIANT GAS RISER DIAGRAM. FBC 107.2.1, FBC FG |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |