2021-03-05 15:29:542ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21021282
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.1: ON THE GAS ISOMETRIC I SEE THAT THE
 REGULATOR HAS BEEN REMOVED FROM THE AREA AT THE GAS
 METER. THIS MAKES THIS APPEARS TO MAKE THE ENTIRE
 SYSTEM A 2 PSI SYSTEM. WAS THE EXISTING SYSTEM A 2 PSI
 SYSTEM? I DO NOT SEE ANY REGULATORS TO DROP THE
 PRESSURE BEFORE THE EXISTING APPLIANCES. THE GAS TABLE
 USED FOR SIZING THIS SYSTEM IS STILL SHOWN TO BE T.
 402.4(2) WHICH IS A LESS THAN 2 PSI TABLE. PLEASE
 RECHECK THE ENTIRE SYSTEM AND PROVIDE A COMPLETE CODE
 COMPLIANT GAS RISER DIAGRAM. FBC 107.2.1, FBC FG
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  