Plan Review Notes
Plan Review Notes For Permit 21021263
Permit Number 21021263
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-03-09 13:09:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO CLEAR INDICATIONS OF WHERE THE FENCING
 WILL BE LOCATED, WHETHER IT IS PERMANENT OR TEMPORARY,
 WHERE ANY GATES WILL BE LOCATED AND THE SIZE OF THOSE
 GATES.
  
 FD EMERGENCY ACCESS ROAD GATES NEED TO BE 20' WIDE.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 2) IT IS RECOMMENDED, NOT REQUIRED, THAT KNOX PADLOCKS
 BE PROVIDED AT EACH GATE FOR FD AFTER HOURS EMERGENCY
 INCIDENT ACCESS, SHOULD THE GATES BE LOCKED AFTER
 HOURS.
  
 KNOX PADLOCKS CAN BE OREDERED AR KNOXLBOX.COM, UNDER
 WEST PALM BEACH FIRE RESCUE.
  
  
  
 3 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  