| Plan Review Notes For Permit 21021258 |
| Permit Number |
21021258 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-05 10:24:48 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2, PLEASE PROVIDE MORE INFORMATION RELATED | | | TO: | | | | | | 1) THE EXTERIOR WALL IN-FILL REPAIR. CONNECTION DETAILS | | | ARE REQUIRED INCLUDING CONNECTORS & FASTENERS ARE | | | REQUIRED TO BE SIGNED & SEALED BY AN ENGINEER OR | | | ARCHITECT. | | | | | | 2) PLEASE PROVIDE THE LOCATION AND SIZE/TYPE OF WINDOW | | | AND/OR DOOR AT EACH OPENING ON LAYOUT SHEET. | | | | | | 3) THE CONTRACTOR MUST SIGN EACH LAYOUT/ SKETCH SHEET | | | SUBMITTED. | | | | | | |
|