| 2021-03-05 17:03:01 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC R TABLE R 301.2(2), THE INDICATED SYSTEM ON THE | | | PRODUCT APPROVAL/NEMO REPORT FOR THE FLAT ROOF DOES NOT | | | APPEAR TO MEET THE WINDLOAD PRESSURES INDICATED WITHIN | | | THE FLORIDA BUILDING CODE. PLEASE PROVIDE AN ENGINEER'S | | | SIGNED/SEALED LETTER WITH WINDLOAD CALCULATIONS AND | | | ROOF MATERIAL ANCHORING PATTERNS. |
|