P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-30 06:37:20 | 1) PROVIDE THE DRAWING SHEET NUMBER FOR THE MATCHLINES | | | ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHOW THE GPM'S THROUGH THE ROOF DRAINS PER | | | FBC-PLUMBING SEC. 1106.2. | | | 3) SHT. P-2.1.A - SHOWS A 1 INCH COLD WATER UP INSIDE | | | STAIRWAY #5. THIS IS NOT PERMITTED PER FBC - BUILDING | | | SEC. 1023.5. | | | 4) SHT. P-2.1.A - THE RAIN WATER LINE APPEARS TO PASS | | | THROUGH STAIR#2. THIS IS NOT PERMITTED PER FBC-BUILDING | | | SEC. 1023.5. | | | 5) SHT.P-2.1.B - SHOWS THE 6 INCH RAIN WATER DRAIN | | | PASSING THROUGH STAIR #1. THIS IS NOT PERMITTED PER | | | FBC-BUILDING SEC.1023.5. | | | 6) THE MAJORITY OF THE PLUMING PLANS ARE MISSING THE | | | KEYNOTE LEGEND FOR THE KEYNOTES ON THE PLANS. PROVIDE | | | THE KEYNOTE LEGEND. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|