| 2021-03-17 16:42:52 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21021222 |
| | 3/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A2: THE NEW PLUMBING RISERS SHOWING 6 IN. SOIL |
| | AND WASTE STACKS DO NOT MATCH WITH THE APPROVED |
| | PLUMBING PLANS THAT WERE SUBMITTED FOR REFERENCE. THE |
| | APPROVED PLANS ON SHEET 301 SHOW 3 AND 4 IN. STACKS. |
| | PLEASE CORRECT THE RISERS AND MARK UP OR HIGHLIGHT THE |
| | REFERENCE PLANS TO SHOW WHICH SANITARY RISER, WATER |
| | RISER, AND FLOOR PLAN ARE BEING RE- DESIGNED- SECTION |
| | 107.2.1 WPB. |
| | |
| | A) BATH #3 RISER: SHOW THE STACK AS A SOLID LINE NOT A |
| | DOTTED VENT LINE. THE SHOWER AND LAV DRAINS SHALL |
| | CONNECT AT ABOVE OR AT THE SAME ELEVATION AS THE WATER |
| | CLOSET FIXTURE DRAIN- SECTION 912.1.1 FBC P. |
| | |
| | B) MASTER BATH RISER: THE SHOWER AND LAV DRAINS SHALL |
| | CONNECT AT ABOVE OR AT THE SAME ELEVATION AS THE WATER |
| | CLOSET FIXTURE DRAIN- SECTION 912.1.1 FBC P. |
| | |
| | 2) A2: PROVIDE A WATER RISER DRAWING- SECTION |
| | 107.3.5.3.1 WPB. |
| | |
| | 3) A2: PROVIDE A SHOWER PAN DETAIL FOR THE MASTER BATH |
| | AND BATH #3- SECTION 421.5.2 FBC P. |
| | |
| | 4) A2: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW SHOWER |
| | VALVES AND DRY SAUNA SHOWING MAKES, MODELS, AND LISTING |
| | AND COMPLIANCE STANDARDS- SECTION 412.3 FBC P. |
| | |
| | 5) A2: SHOW THE LOCATION OF THE DISHWASHER AND |
| | REFRIGERATOR AND SHOW WATER SUPPLY CONNECTIONS AND |
| | REQUIRED DEVICES- WATER HAMMER ARRESTORS, BACKFLOW |
| | PREVENTERS- SECTION 608.3 FBC P. |
| | |
| | 6) A2: RELOCATING THE SHOWER DRAIN OUTLETS MAY REQUIRE |
| | THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 7) A2: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | 8) A2: REFER TO SECTION 1002.1: THE HORIZONTAL DISTANCE |
| | FROM THE CENTERLINE OF THE NEW SHOWER DRAIN OUTLET TO |
| | THE CENTERLINE OF THE INLET OF THE EXISTING TRAPS SHALL |
| | NOT EXCEED 30". PLEASE PLACE A NOTE ON THE PLAN |
| | INDICATING COMPLIANCE. |
| | |
| | 9) 2) FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE |
| | THE BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE |
| | ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND |
| | THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING |
| | UNITS, THE PROPOSED ALTERATIONS SHALL ALSO BE IN |
| | COMPLIANCE WITH THE FAIR HOUSING ACT. THE FAIR HOUSING |
| | ACCESSIBILITY GUIDELINES ARE INCLUDED IN THE FLORIDA |
| | ACCESSIBILITY CODE- 2017 SIXTH EDITION. REFER TO |
| | REQUIRMENT 7 USUABLE KITCHENS AND BATHROOMS AND PAGE |
| | 7.33 IN THE FAIR HOUSING ACT DESIGN MANUAL. THE |
| | DESIGNER OF RECORD SHALL INDICATE ON THE REVISED PLANS |
| | WHICH BATHROOM SPECIFICATION- TYPE A OR TYPE B WAS USED |
| | IN THE ORIGINAL DESIGN. THE DESIGNER OF RECORD FOR THE |
| | PROJECT IS ADVISED TO DO A RECORDS REQUEST OF THE |
| | ORIGINAL APPROVED PLANS TO MAKE THAT DETERMINATION. |
| | RECORDS REQUESTS CAN BE ACCESSED ON THE CITY OF WEST |
| | PALM BEACH WEBSITE UNDER DEVELOPMENT SERVICES. THE |
| | ORIGINAL DESIGN INTENT NEEDS TO BE KNOWN IN ORDER TO |
| | ENSURE THE ALTERATIONS WILL BE IN COMPLIANCE. |
| | |
| | REFER TO PAGES 7.33- 7.83 FOR COMPLETE GUIDELINES AND |
| | PROVIDE ENLARGED DIMENSIONED BATHROOM DRAWINGS AND |
| | DETAILS- CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS, |
| | KNEE AND TOE CLEARANCES, FAUCET AND CONTROL VALVE |
| | LOCATIONS, GRAB BARS AND GRAB REINFPORCEMENTS ETC. |
| | |
| | PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| | GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| | DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| | A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| | ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| | THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| | REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| | SO REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| | PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| | COPY OF THE FAIR HOUSING AFFIDAVIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |