2021-03-03 15:40:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE IS INDICATIONUNDER FIRE SPRINKLER
 NOTE: "EXISTING FIRE SPRINKLER (NO CHANGE)" HOWEVER,
 THERE IS EXTENSIVE REMODLING WITH NUMOURUS WALL BEING
 CHANGE AND NEW ROOMS BEING ADDED.
  
 THESE NEW AREAS REQUIRE FIRE SPRINKLER PROTECTION AND
 POSSIBLY FIRE ALARM EQUIPMENT.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE
 STATEMENTS AND ENSURE PROPER PERMITTING IS SUBMITTED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  