2021-05-05 11:48:32CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 PERMIT 21021166
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SCOPE OF WORK NOT CLEAR. APPLICATION ONLY MENTIONS A
 NEW ELECTRICAL SERVICE, BUT DRAWINGS SEEM TO INDICATE
 ADDITIONAL ELECTRICAL WORK BEING DONE (NEW LIGHTS,
 RECEPTACLES, EQUIPMENT, ETC)
  
 PLEASE INDICATE CLEARLY THE SCOPE OF WORK. THE
 APPLICATION ONLY MENTIONS A NEW ELECTRICAL SERVICE BUT
 THERE IS A LOT OF OTHER ELECTRICAL WORK ON DRAWINGS.
 INDICATE WHAT IS EXISTING OR WHAT IS NOT COVERED UNDER
 THIS PERMIT.
  
 2) SHEET E-03 (ELECTRICAL RISER DIAGRAMS) : GROUNDING
 ELECTRODE CONDUCTOR TO EXISTING WATER PIPE MUST BE AT
 LEAST #4 CU OR #2 AL FOR SERVICE CONDUCTORS #3/0 AND
 ABOVE. NEC 250.66
  
 NOT CORRECTED.
  
 3) PLEASE CHANGE CODE REFERENCES TO NEC 2017 AND FBC
 2020, 7TH EDITION FBC 107
  
 NOT CORRECTED'
  
 4) PLEASE SEE SIGNATURE COMMENTS.
  
 CORRECTED FOR ELECTRICAL DRAWINGS
  
 5) IT SEEMS THAT DUPLICATE DRAWINGS HAVE BEEN UPLOADED
 (THERE ARE THREE E-01S, TWO E-02S, AND TWO E-03S).
 PLEASE CLARIFY WHICH VERSIONS ARE THE ONES THAT NEED TO
 BE REVIEWED AND REMOVE THE ONES THAT SHOULD NOT BE
 USED. FBC
  
 PARTIALLY CORRECTED. DUPLICATE DRAWINGS STILL PRESENT.
  
 6) SHEET E-2 MENTIONS THAT NEW ELECTRIC SERVICE IS
 UNDERGROUND BY FPL BUT SHEET E-3 (ELECTRICAL RISER
 DIAGRAM #3) SAYS THAT SERVICE IS OVERHEAD. PLEASE
 CLARIFY AND CORRECT. FBC 107
  
  
 7) SHEET E-2: THERE IS A NOTE THAT READS ELECTRICAL
 PANEL. WHICH PANEL IS THIS? IS IT ELECTRICAL PANEL A?
  
 PLEASE SHOW LOCATION OF ALL PANELS AND CLEARLY LABELED
 THEM
  
 8) NEW COMMENT
  
 ELECTRICAL DRAWINGS CAN NOT BE APPROVED UNTIL ADDRESS
 COMMENTS ARE RESOLVED.
  
 END OF COMMENTS.
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 PHONE 561-805-6746.
 EMAIL: [email protected]
  