| 2021-05-05 11:48:32 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | PERMIT 21021166 |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SCOPE OF WORK NOT CLEAR. APPLICATION ONLY MENTIONS A |
| | NEW ELECTRICAL SERVICE, BUT DRAWINGS SEEM TO INDICATE |
| | ADDITIONAL ELECTRICAL WORK BEING DONE (NEW LIGHTS, |
| | RECEPTACLES, EQUIPMENT, ETC) |
| | |
| | PLEASE INDICATE CLEARLY THE SCOPE OF WORK. THE |
| | APPLICATION ONLY MENTIONS A NEW ELECTRICAL SERVICE BUT |
| | THERE IS A LOT OF OTHER ELECTRICAL WORK ON DRAWINGS. |
| | INDICATE WHAT IS EXISTING OR WHAT IS NOT COVERED UNDER |
| | THIS PERMIT. |
| | |
| | 2) SHEET E-03 (ELECTRICAL RISER DIAGRAMS) : GROUNDING |
| | ELECTRODE CONDUCTOR TO EXISTING WATER PIPE MUST BE AT |
| | LEAST #4 CU OR #2 AL FOR SERVICE CONDUCTORS #3/0 AND |
| | ABOVE. NEC 250.66 |
| | |
| | NOT CORRECTED. |
| | |
| | 3) PLEASE CHANGE CODE REFERENCES TO NEC 2017 AND FBC |
| | 2020, 7TH EDITION FBC 107 |
| | |
| | NOT CORRECTED' |
| | |
| | 4) PLEASE SEE SIGNATURE COMMENTS. |
| | |
| | CORRECTED FOR ELECTRICAL DRAWINGS |
| | |
| | 5) IT SEEMS THAT DUPLICATE DRAWINGS HAVE BEEN UPLOADED |
| | (THERE ARE THREE E-01S, TWO E-02S, AND TWO E-03S). |
| | PLEASE CLARIFY WHICH VERSIONS ARE THE ONES THAT NEED TO |
| | BE REVIEWED AND REMOVE THE ONES THAT SHOULD NOT BE |
| | USED. FBC |
| | |
| | PARTIALLY CORRECTED. DUPLICATE DRAWINGS STILL PRESENT. |
| | |
| | 6) SHEET E-2 MENTIONS THAT NEW ELECTRIC SERVICE IS |
| | UNDERGROUND BY FPL BUT SHEET E-3 (ELECTRICAL RISER |
| | DIAGRAM #3) SAYS THAT SERVICE IS OVERHEAD. PLEASE |
| | CLARIFY AND CORRECT. FBC 107 |
| | |
| | |
| | 7) SHEET E-2: THERE IS A NOTE THAT READS ELECTRICAL |
| | PANEL. WHICH PANEL IS THIS? IS IT ELECTRICAL PANEL A? |
| | |
| | PLEASE SHOW LOCATION OF ALL PANELS AND CLEARLY LABELED |
| | THEM |
| | |
| | 8) NEW COMMENT |
| | |
| | ELECTRICAL DRAWINGS CAN NOT BE APPROVED UNTIL ADDRESS |
| | COMMENTS ARE RESOLVED. |
| | |
| | END OF COMMENTS. |
| | |
| | |