| 2021-03-19 15:34:58 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | PERMIT 21021166 |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SCOPE OF WORK NOT CLEAR. APPLICATION MENTIONS A NEW |
| | ELECTRICAL SERVICE, BUT DRAWINGS SEEM TO INDICATE |
| | ADDITIONAL ELECTRICAL WORK BEING DONE (NEW LIGHTS, |
| | RECEPTACLES, EQUIPMENT, ETC) |
| | 2) SHEET E-03 (NEW ELECTRICAL RISER DIAGRAM #3): |
| | GROUNDING ELECTRODE CONDUCTOR TO EXISTING WATER PIPE |
| | MUST BE AT LEAST #4 CU OR #2 AL. NEC 250.66 |
| | 3) PLEASE CHANGE CODE REFERENCES TO NEC 2017 AND FBC |
| | 2020, 7TH EDITION FBC 107 |
| | 4) PLEASE SEE SIGNATURE COMMENTS. |
| | 5) IT SEEMS THAT DUPLICATE DRAWINGS HAVE BEEN UPLOADED |
| | (THERE ARE THREE E-01S, TWO E-02S, AND TWO E-03S). |
| | PLEASE CLARIFY WHICH VERSIONS ARE THE ONES THAT NEED TO |
| | BE REVIEWED AND REMOVE THE ONES THAT SHOULD NOT BE |
| | USED. FBC |
| | 6) SHEET E-2 MENTIONS THAT NEW ELECTRIC SERVICE IS |
| | UNDERGROUND BY FPL BUT SHEET E-3 (ELECTRICAL RISER |
| | DIAGRAM #3) SAYS THAT SERVICE IS OVERHEAD. PLEASE |
| | CLARIFY AND CORRECT. FBC 107 |
| | 7) SHEET E-2: THERE IS A NOTE THAT READS ?ELECTRICAL |
| | PANEL?. WHICH PANEL IS THIS? IS IT ELECTRICAL PANEL A? |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| | MS |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | DEVELOPMENT SERVICES |
| | CITY OF WEST PAM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | |
| | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, |
| | PHONE 561-805-6746. |
| | EMAIL: [email protected] |
| | |