2021-03-19 15:34:58CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 PERMIT 21021166
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SCOPE OF WORK NOT CLEAR. APPLICATION MENTIONS A NEW
 ELECTRICAL SERVICE, BUT DRAWINGS SEEM TO INDICATE
 ADDITIONAL ELECTRICAL WORK BEING DONE (NEW LIGHTS,
 RECEPTACLES, EQUIPMENT, ETC)
 2) SHEET E-03 (NEW ELECTRICAL RISER DIAGRAM #3):
 GROUNDING ELECTRODE CONDUCTOR TO EXISTING WATER PIPE
 MUST BE AT LEAST #4 CU OR #2 AL. NEC 250.66
 3) PLEASE CHANGE CODE REFERENCES TO NEC 2017 AND FBC
 2020, 7TH EDITION FBC 107
 4) PLEASE SEE SIGNATURE COMMENTS.
 5) IT SEEMS THAT DUPLICATE DRAWINGS HAVE BEEN UPLOADED
 (THERE ARE THREE E-01S, TWO E-02S, AND TWO E-03S).
 PLEASE CLARIFY WHICH VERSIONS ARE THE ONES THAT NEED TO
 BE REVIEWED AND REMOVE THE ONES THAT SHOULD NOT BE
 USED. FBC
 6) SHEET E-2 MENTIONS THAT NEW ELECTRIC SERVICE IS
 UNDERGROUND BY FPL BUT SHEET E-3 (ELECTRICAL RISER
 DIAGRAM #3) SAYS THAT SERVICE IS OVERHEAD. PLEASE
 CLARIFY AND CORRECT. FBC 107
 7) SHEET E-2: THERE IS A NOTE THAT READS ?ELECTRICAL
 PANEL?. WHICH PANEL IS THIS? IS IT ELECTRICAL PANEL A?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 PHONE 561-805-6746.
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved