2021-03-10 16:28:40****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2; THE SUBMITTED NOA & PRODUCT APPROVAL
 APPEAR TO BE MARKED INCORRECTLY.
  
 PLEASE CORRECT AND RE-SUBMIT THE FOLLOWING:
  
 1) MIAMI DADE NOA: PAGE 1 INDICATES THAT NEW WINDOWS AT
 OPENINGS #2 & 3 ARE TO BE INSTALLED, WHILE THE DRAWING
 SP-1 AND SCHEDULE INDICATE THAT NEW WINDOWS ARE TO BE
 INSTALLED AT OPENINGS #4 & 12.
  
 2) PGTS PRODUCT APPROVAL PAGE 1 INDICATES THAT THPE XO
 HORIZONTAL ROLLER WINDOWS ARE TO BE INSTALLED. THE #4 &
 12 OPENING WIDTHS ARE 110" & 110.5" WHILE THE MAXIMUM
 ALLOWED WITH FOR THE TYPE XO WINDOWS IS 76" OVERALL.
 PLEASE CORRECT THE TYPE OF WINDOWS TO BE INSTALLED AS
 IT APPEARS THAT THE TYPE XOX WINDOWS MEET THE REQUIRED
 WIDTHS.
  
  
  