| Plan Review Notes For Permit 21021164 |
| Permit Number |
21021164 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-10 16:28:40 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2; THE SUBMITTED NOA & PRODUCT APPROVAL | | | APPEAR TO BE MARKED INCORRECTLY. | | | | | | PLEASE CORRECT AND RE-SUBMIT THE FOLLOWING: | | | | | | 1) MIAMI DADE NOA: PAGE 1 INDICATES THAT NEW WINDOWS AT | | | OPENINGS #2 & 3 ARE TO BE INSTALLED, WHILE THE DRAWING | | | SP-1 AND SCHEDULE INDICATE THAT NEW WINDOWS ARE TO BE | | | INSTALLED AT OPENINGS #4 & 12. | | | | | | 2) PGTS PRODUCT APPROVAL PAGE 1 INDICATES THAT THPE XO | | | HORIZONTAL ROLLER WINDOWS ARE TO BE INSTALLED. THE #4 & | | | 12 OPENING WIDTHS ARE 110" & 110.5" WHILE THE MAXIMUM | | | ALLOWED WITH FOR THE TYPE XO WINDOWS IS 76" OVERALL. | | | PLEASE CORRECT THE TYPE OF WINDOWS TO BE INSTALLED AS | | | IT APPEARS THAT THE TYPE XOX WINDOWS MEET THE REQUIRED | | | WIDTHS. | | | | | | | | | |
|