Plan Review Notes
Plan Review Notes For Permit 21021162
Permit Number 21021162
Review Stop B
Sequence Number 2
Notes
Date Text
2021-03-04 11:32:44PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER SHALL SELECT THE SYSTEM TO BE IN STALLED.
 PROVIDE THE BUILDING EXPOSURE.
 LIMITATION #7 SHALL APPLY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NEW COMMENTS:
  
 2. TRINITY EVALUATION REPORT UPLOADED ON 3/2/21 FOR
 PRODUCT APPROVAL FL2533-R16 HAS EXPIRED. PROVIDE A
 PRODUCT APPROVAL APPROVED UNDER THE 2020 FBC 7TH ED.
 INCLUDE COVER PAGE, EVALUATION REPORT WITH SYSTEM
 IDENTIFIED TO BE INSTALLED AND INSTALATION
 INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  