| Plan Review Notes For Permit 21021094 |
| Permit Number |
21021094 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-02 09:21:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE HAS TO INCLUDE ALL MATERIALS AND | | | EQUIPMENT.(1500) | | | | | | 2) ATS CAN NOT BE PROTECTED BY A 200A BREAKER. | | | | | | 3) ATS DOES NOT HAVE TO BE SERVICE ENTRANCE RATED, IT | | | IS AFTER THE FIRST MEANS OF DISCONNECT. |
|