2021-03-01 08:26:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY ON THE GENERATOR LOCATION THAT THE GENERATOR
 EXHAUST IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS TO
 A STRUCTURE. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL
 AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) THE ELEVATED GENERATOR SLAB, FOUNDATION AND WALLS
 REQUIRE STEEL REINFORCEMENT. SPECIFY THE REBAR SIZE AND
 SPACING ON THE DRAWINGS. FBC 107.2.1
 I AM NOT SURE WHY THE GENERATOR IS BEING ELEVATED. THE
 PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA
 AND IS NOT REQUIRED TO BE ELEVATED BY THE BUILDING CODE
 OR CITY'S FLOOD ORDINANCE.
  
  