| Plan Review Notes For Permit 21021094 |
| Permit Number |
21021094 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-01 08:26:57 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY ON THE GENERATOR LOCATION THAT THE GENERATOR | | | EXHAUST IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS TO | | | A STRUCTURE. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL | | | AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE | | | LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY | | | HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS. | | | | | | 2) THE ELEVATED GENERATOR SLAB, FOUNDATION AND WALLS | | | REQUIRE STEEL REINFORCEMENT. SPECIFY THE REBAR SIZE AND | | | SPACING ON THE DRAWINGS. FBC 107.2.1 | | | I AM NOT SURE WHY THE GENERATOR IS BEING ELEVATED. THE | | | PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | AND IS NOT REQUIRED TO BE ELEVATED BY THE BUILDING CODE | | | OR CITY'S FLOOD ORDINANCE. | | | | | | |
|