Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-02-24 16:00:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO INDICATIONS ON THIS SUBMITTAL OF
 EXISTING FIRE SPRINKLER NOR FIRE ALARM SYSTEMS.
  
 PREVIOUS RECORDS INDICATE THAT BOTH ARE PRESENT.
  
 PLEASE REVIEW AND PROVIDE ACCURATE INFORMATION,
  
  
 2) ANY REMOVAL OF WALLS, NEW WALLS OR A RECONSTRUCTION
 OF AREAS REQUIRES A REVIEW OF THE FIRE SPRINKLER & FIRE
 ALARM PROTECTION SYSTEMS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER & FIRE ALARM
 SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS BY CERTIFIED FIRE SPRINKLER CONTRACTORS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  