Plan Review Notes
Plan Review Notes For Permit 21020978
Permit Number 21020978
Review Stop E
Sequence Number 1
Notes
Date Text
2021-03-12 08:29:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) WHAT SIZE IS THE SERVICE? 150A???
  
 2) PANEL SHOWS MAIN LUG ONLY, PANEL IS REQUIRED TO HAVE
 MAIN.
  
 3) LOCATION OF PANEL WILL REQUIRE FEEDER TO BE
 UNDERGROUND OR ENCASED IN 2" OF CONCRETE. 230.6
  
 4) SMOKE ALARM IN BDRM #1 TO CLOSE TO BATHROOM DOOR
 REQUIRED TO BE AT LEAST 3' AWAY. FBC R314
  
 5) EGRESS DOOR FROM BDRM #1 NEEDS A SWITCH AND LIGHT
 210.70(A)(2)
  
 6) LOAD CALCULATION DOES NOT INCLUDE 2 SMALL APPLIANCE
 CIRCUITS AS REQUIRED BY 210.11(C)(7)
  
 7) NOTE #7 SHALL INCLUDE LAUNDRY AREA IN GFCI
 PROTECTION.
  
 8) NOTE #24 NEEDS TO INCLUDE ALL ROOMS REQUIRED BY
 210.12(A)
  
 9) NO TELEPHONE OUTLET(S) SHOWN ON PLAN AT LEAST ONE
 SHALL BE INSTALL PER 800.156
  
  