| 2021-03-11 15:37:19 | GUEST HOUSE ADDITION/REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT FBC WPB AMENDMENTS 107.1 IF THE DESIGN |
| | PROFESSIONAL IS AN ARCHITECT, INTERIOR DESIGNER, |
| | LANDSCAPE ARCHITECT , OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE |
| | PRACTICE OF ARCHITECTURE OR INTERIOR DESIGN AS |
| | PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART I, |
| | OR LANDSCAPE ARCHITECTURE AS PROVIDED FOR |
| | IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, |
| | FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA, AS REQUIRED BY |
| | FLORIDA STATUTE. |
| | 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, |
| | EXTERIOR DOORS AND ROOFING SYSTEMS. |
| | 3) ROOFING SYSTEMS AND WINDOW AND DOOR PRODUCT |
| | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |