Plan Review Notes
Plan Review Notes For Permit 21020961
Permit Number 21020961
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-17 05:55:551ST REVIEW FBC-2020 PLUMBING
 PERMIT-21020961
 3/17/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- WE ARE CURRENTLY IN THE SEVENTH EDITION OF THE 2020
 OF THE FLORIDA BUILDING CODE, THERE ARE LOCATIONS ON
 MEP1.0 THAT QUOTE PREVIOUS YEARS CODE SECTION AND NEED
 TO BE CORRECTED TO REFLECT THE CURRENT CODE CYCLE.
  
 2- SIGNED AND SEALED DRAWINGS AND DOCUMENTS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ENGINEER OR ARCHITECT DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - PLEASE
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST
 FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT
 OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY E MAILING [email protected] AND ASKING FOR THE FORM.
  
 3- SHOW ALL PIPE SIZES FOR EACH PIPE ON THE SANITARY
 RISER DIAGRAM ON MEP1.0. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4- A WATER RISER DIAGRAM SHALL BE ON THE PLANS CLEARLY
 INDICATING HOW THE NEW BATHROOM WILL BE CONNECTED TO
 THE EXISTING HOME. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5- FBC P 607.2HOT OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 6- FBC P 607.5INSULATION OF PIPING.
 FOR OTHER THAN GROUP R2, R3 AND R4 OCCUPANCIES THAT ARE
 THREE STORIES OR LESS IN HEIGHT ABOVE GRADE PLANE,
 PIPING TO THE INLET OF A WATER HEATER AND PIPING
 CONVEYING WATER HEATED BY A WATER HEATER SHALL BE
 INSULATED IN ACCORDANCE WITH SECTION C404.4 OF THE
 FLORIDA BUILDING CODE, ENERGY CONSERVATION. FOR GROUP
 R2, R3 AND R4 OCCUPANCIES THAT ARE THREE STORIES OR
 LESS IN HEIGHT ABOVE GRADE PLANE, PIPING TO THE INLET
 OF A WATER HEATER AND PIPING CONVEYING WATER HEATED BY
 A WATER HEATER SHALL BE INSULATED IN ACCORDANCE WITH
 SECTION R403.5.3 OF THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION
  
 7- SANTARY SEWER DIAGRAM SHALL BE ON THE PLANS CLEARLY
 INDICATING THE HOW THE NEW BATHROOM WILL BE CONNECTED
 TO THE EXISTING HOME. THIS CAN BE DONE ON A SURVEY FLAT
 DRAWING OF THE PROPERTY. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8- IT APEARS AS THOUGH THE TOP PORTION ON G1.0 IS
 MISSING ON THE SUBMITTED PLANS. WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  