| Date |
Text |
| 2021-04-15 10:52:28 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21020946 |
| | ADD: 1700 45TH ST. TENANT SUITE NUMBER # 1670 / AUTO |
| | ZONE |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 901-485-6906 - KATIE MITCHELL |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. APRIL 15TH/ 2021 |
| | |
| | ACTION: DENIED |
| | 1-2) COMPLIED. |
| | |
| | 3) SHEET A-1 THE FLOOR PLAN: |
| | 3A) COMPLIED. |
| | |
| | 3B) NOTICE ONLY. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 105.2.6. RACK STORAGE OVER 5FEET 9 INCHES TALL REQUIRES |
| | A SEPARATE RACK STORAGE PERMIT, WITH PLANS REVIEW, AND |
| | ASSOCIATED FEES. |
| | |
| | 3C) COMPLIED. |
| | |
| | 3D) 3RD REQUEST. SEMI-COMPLIED. SHEET A-1 NOW SHOWS A |
| | SECOND LINE ON EACH SIDE OF THE RAMP BUT DOES NOT |
| | PROVIDE A CROSS SECTION OF THE RAMP AND CURB SHOWING |
| | COMPLIANCE WITH 2020 FBC-ACCESSIBILITY CODE SECTION |
| | 1012.10 EDGE PROTECTION FOR THE RAMP. AN ATTEMPT IN |
| | DETAILING THE CONDITION FOR THE RAISED EDGE PROTECTION |
| | OF THE RAMP WAS MADE. THIS REVIEW A CUT SECTION THROUGH |
| | THE LENGTH OF THE RAMP AND LANDINGS WAS MADE. THIS CUT |
| | SECTION DOES NOT HIGHLIGHT THE PROPOSED RAISED EDGE |
| | PROTECTION OF THE RAMP. A CUT SECTION THROUGH THE RAMP |
| | 90 DEGREES TO THE RUN OR LENGTH OF THE RAMP IS WHAT IS |
| | REQUIRED. |
| | |
| | 4) COMPLIED. |
| | 4A-B) COMPLIED. |
| | |
| | 5) 3RD REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | FL14218 YHS 50 FS STOREFRONT SYSTEM INSIDE GLAZED. |
| | 17-PAGE REPORT. GLAZING TYPE NOT IDENTIFIED NOR WIDTH |
| | NOR HEIGHT NOR MULLION TRIBUTARY AREA NOR PRESSURES FOR |
| | BOTH. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) BUILDING PROVISO: SHEET S1.1 SHOWS NEW STEEL SUPPORT |
| | ANGLES AND STEEL DECKING. THE DETAILS SHOW WHERE |
| | JOBSITE WELDING WILL BE REQUIRED FOR THE NEW ROOF TOP |
| | MECHANICAL EQUIPMENT. |
| | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| | FRAMING INSPECTION. NO SPECIAL INSPECTION FORM IS |
| | REQUIRED. IN FLORIDA THE TERM SPECIAL INSPECTOR REFERS |
| | TO BUILDING THAT ARE CONSIDERED THRESHOLD BUILDINGS 3 |
| | STORIES IN HEIGHT THAT WILL REQUIRE A THRESHOLD |
| | INSPECTOR/ SPECIAL INSPECTOR. THIS IS A SPECIAL |
| | INDORSEMENT THAT STRUCTURAL P. E. CAN ACHIEVE. IF |
| | FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666 FOR ADDITIONAL INFORMATION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2020 FBC-B 2204.2 BOLTING. |
| | |
| | 10A) COMPLIED. |
| | |
| | 10B) 3RD REQUEST. SEMI-COMPLIED. SHEET A-3 NEW EXTERIOR |
| | ROOF TOP ACCESS LADDER TO ROOF. NEW COMMENT ON PLANS |
| | STATES GC TO CONSTRUCT PER DETAIL 10. PLEASE NOTE THAT |
| | PERMANENT ROOF TOP ACCESS LADDERS TO THE ROOF ARE |
| | PRE-ENGINEERED AT A FACTORY AND SHOP DRAWING1ST REVIEW |
| | COMMENT. 700SHEETS SENT TO THE DESIGNER OF RECORD FOR |
| | REVIEW AND APPROVAL. ONCE THEY RECEIVE THE EITHER |
| | ARCHITECT OR ENGINEERS SHOP DRAWING STAMP OF APPROVAL |
| | THEN THE START OF MANUFACTURING THIS LADDER BEGINS. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. THIS CAN BE A BUILDING PROVISO / |
| | DEFERRED SUBMITTAL. SUBMITTED AFTER PERMIT ISSUANCE. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 1ST ROUND OF COMMENTS. 2017 FBC-B 1011.16 LADDERS. |
| | PERMANENT LADDERS SHALL NOT SERVE AS A PART OF THE |
| | MEANS OF EGRESS FROM OCCUPIED SPACES WITHIN A BUILDING. |
| | PERMANENT LADDERS SHALL BE PERMITTED TO PROVIDE ACCESS |
| | TO THE FOLLOWING AREAS: |
| | 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE, |
| | REPAIR OR MONITORING OF EQUIPMENT. |
| | 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE |
| | STAIRWAY ACCESS IN ACCORDANCE WITH SECTION |
| | 1011.12.1. |
| | 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 306.5 OF THE FLORIDA BUILDING CODE, |
| | MECHANICAL. |
| | |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |