Plan Review Notes
Plan Review Notes For Permit 21020946
Permit Number 21020946
Review Stop B
Sequence Number 3
Notes
Date Text
2021-04-15 10:52:28WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020946
 ADD: 1700 45TH ST. TENANT SUITE NUMBER # 1670 / AUTO
 ZONE
 CONT: TBD/ TO BE DETERMINED
 TEL: 901-485-6906 - KATIE MITCHELL
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. APRIL 15TH/ 2021
  
 ACTION: DENIED
 1-2) COMPLIED.
  
 3) SHEET A-1 THE FLOOR PLAN:
 3A) COMPLIED.
  
 3B) NOTICE ONLY. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 105.2.6. RACK STORAGE OVER 5FEET 9 INCHES TALL REQUIRES
 A SEPARATE RACK STORAGE PERMIT, WITH PLANS REVIEW, AND
 ASSOCIATED FEES.
  
 3C) COMPLIED.
  
 3D) 3RD REQUEST. SEMI-COMPLIED. SHEET A-1 NOW SHOWS A
 SECOND LINE ON EACH SIDE OF THE RAMP BUT DOES NOT
 PROVIDE A CROSS SECTION OF THE RAMP AND CURB SHOWING
 COMPLIANCE WITH 2020 FBC-ACCESSIBILITY CODE SECTION
 1012.10 EDGE PROTECTION FOR THE RAMP. AN ATTEMPT IN
 DETAILING THE CONDITION FOR THE RAISED EDGE PROTECTION
 OF THE RAMP WAS MADE. THIS REVIEW A CUT SECTION THROUGH
 THE LENGTH OF THE RAMP AND LANDINGS WAS MADE. THIS CUT
 SECTION DOES NOT HIGHLIGHT THE PROPOSED RAISED EDGE
 PROTECTION OF THE RAMP. A CUT SECTION THROUGH THE RAMP
 90 DEGREES TO THE RUN OR LENGTH OF THE RAMP IS WHAT IS
 REQUIRED.
  
 4) COMPLIED.
 4A-B) COMPLIED.
  
 5) 3RD REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 FL14218 YHS 50 FS STOREFRONT SYSTEM INSIDE GLAZED.
 17-PAGE REPORT. GLAZING TYPE NOT IDENTIFIED NOR WIDTH
 NOR HEIGHT NOR MULLION TRIBUTARY AREA NOR PRESSURES FOR
 BOTH.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) BUILDING PROVISO: SHEET S1.1 SHOWS NEW STEEL SUPPORT
 ANGLES AND STEEL DECKING. THE DETAILS SHOW WHERE
 JOBSITE WELDING WILL BE REQUIRED FOR THE NEW ROOF TOP
 MECHANICAL EQUIPMENT.
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION. NO SPECIAL INSPECTION FORM IS
 REQUIRED. IN FLORIDA THE TERM SPECIAL INSPECTOR REFERS
 TO BUILDING THAT ARE CONSIDERED THRESHOLD BUILDINGS 3
 STORIES IN HEIGHT THAT WILL REQUIRE A THRESHOLD
 INSPECTOR/ SPECIAL INSPECTOR. THIS IS A SPECIAL
 INDORSEMENT THAT STRUCTURAL P. E. CAN ACHIEVE. IF
 FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666 FOR ADDITIONAL INFORMATION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2020 FBC-B 2204.2 BOLTING.
  
 10A) COMPLIED.
  
 10B) 3RD REQUEST. SEMI-COMPLIED. SHEET A-3 NEW EXTERIOR
 ROOF TOP ACCESS LADDER TO ROOF. NEW COMMENT ON PLANS
 STATES GC TO CONSTRUCT PER DETAIL 10. PLEASE NOTE THAT
 PERMANENT ROOF TOP ACCESS LADDERS TO THE ROOF ARE
 PRE-ENGINEERED AT A FACTORY AND SHOP DRAWING1ST REVIEW
 COMMENT. 700SHEETS SENT TO THE DESIGNER OF RECORD FOR
 REVIEW AND APPROVAL. ONCE THEY RECEIVE THE EITHER
 ARCHITECT OR ENGINEERS SHOP DRAWING STAMP OF APPROVAL
 THEN THE START OF MANUFACTURING THIS LADDER BEGINS. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC. THIS CAN BE A BUILDING PROVISO /
 DEFERRED SUBMITTAL. SUBMITTED AFTER PERMIT ISSUANCE.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 1ST ROUND OF COMMENTS. 2017 FBC-B 1011.16 LADDERS.
 PERMANENT LADDERS SHALL NOT SERVE AS A PART OF THE
 MEANS OF EGRESS FROM OCCUPIED SPACES WITHIN A BUILDING.
 PERMANENT LADDERS SHALL BE PERMITTED TO PROVIDE ACCESS
 TO THE FOLLOWING AREAS:
 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE,
 REPAIR OR MONITORING OF EQUIPMENT.
 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE
 STAIRWAY ACCESS IN ACCORDANCE WITH SECTION
 1011.12.1.
 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 306.5 OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  