| 2021-04-07 11:24:50 | 1) SHT. A-5 - SHOW THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSETS ON THE PLAN. COMPLY WITH FBC-ACCESS. SEC. |
| | 604.3.1. SHOW THE REQUIRED CLEARANCE ON THE PLANS.2ND |
| | REQUEST. |
| | 2) SHT. A-2 - DETAIL #8 - THE HEIGHT OF THE LAVATORY |
| | FROM THE FINISH FLOOR APPEARS TO BE MEASURED TO THE |
| | BACK OF THE LAVATORY. LAVATORIES SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOOR OR |
| | GROUND. FBC-ACCESS. SEC.606.3. |
| | 3) SHT. P-1 STILL SHOWS THE BACKFLOW PREVENTION DEVICE |
| | YET THE RESPONSE NARRATIVE STATES THE DEVICE HAS BEEN |
| | REMOVED. CLARIFY. |
| | 4) THE PLUMBING SHEET IS NOT DIGITALLY SIGNED AND |
| | SEALED AS REQUIRED BY FL. ADMIN. CODE RULE |
| | 61G15-23.004, 61G15-23.005. 2ND REQUEST. |
| | 5) PROVIDE A SLAB REPAIR DETAIL FOR REVIEW. THE |
| | RESPONSE STATING THE DETAIL TO BE PROVIDED BY OTHERS IS |
| | NOT ACCEPTABLE. WPB AMEND. TO FBC SEC. 107.2.1. 2ND |
| | REQUEST. |
| | 6) SHT. P-1 - THE DRINKING FOUNTAIN CANNOT DISCHARGE |
| | INTO THE HORIZONTAL WET VENT. FBC-PLUMBING SEC.912.1. |
| | 2ND REQUEST. |
| | 7) SHT. P-1 - DETAIL #7 - THE WATER CLOSETS ARE STLL |
| | SHOWN AS BEING LOCATED 1'-11" TO THE CENTERLINE OF THE |
| | WATER CLOSETS. THE REQUIRED DIMENSION SHALL BE 16"-18" |
| | TO THE CENTERLINE OF THE WATER CCLSET FROM THE ADJACENT |
| | WALL. FBC-ACCESS. SEC. 604.2.2ND REQUEST. |
| | 8) SHT. P-1 - DETAIL #6 - NOTE "B". THE THICKNESS OF |
| | THE INSULATION ON THE HOT WATER PIPING SHALL COMPLY |
| | WITH FBC-ENERGY TABLE C403.2.10. THE MINIMUM THICKNESS |
| | SHALL BE 1 INCH. |
| | 9) THE RESPONSE NARRATIVE STATES A CONDENSATE DRAINAGE |
| | SYSTEM HAS BEEN INCLUDED ON THE PLANS BUT I COULD NOT |
| | LOCATE. SPECIFY HICH SHEET THE PLAN IS ON. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | |