2021-03-30 12:36:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020946
 ADD: 1670 45TH ST. TENANT SUITE NUMBER???? / AUTO ZONE
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 29TH/ 2021
  
 ACTION: DENIED
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST. THE PERMIT APPLICATION NOR THE
 TITLEBLOCK PROVIDE THE TENANT SUITE/ UNIT ADDRESS. WHEN
 WE VIEW ( GOGGLE MAPS) THE ADDRESS OF 1670 45TH ST THIS
 IS FOR THE WHOLE SHOPPING CENTER, NOT THIS TENANT
 SPACE.
  
 2020 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) SHEET A0- COVER: COMPLIED.
  
 3) SHEET A-1 THE FLOOR PLAN:
 3A) SEMI-COMPLIED. THIS FLOOR PLAN NOW SHOWS A NEW EXIT
 DOORWAY AT THE REAR OF THE BUILDING. THE QUESTION
 REMAINS IS THE EXIT SIGN MOUNTED TO THE WALL OR
 CEILING. AT WHAT HEIGHT IS THE CEILING, THE RACK
 STORAGE IS 7SEET 6 INCHES TALL. THE OTHER ISSUE IS THIS
 REVISED ARCHITECTURAL PLAN WAS NOT CARRIED OVER ONTO
 SHEET E3 THERE IS NO EXIT DOORWAY OR EXIT LIGHT SHOWN
 FOR THE NEW EXIT DOORWAY. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. CORELATE PLANS TO SHOW THE
 SAME DETAILS.
  
 1ST ROUND OF COMMENTS. THERE IS NO LIFE SAFETY SHEET,
 JUST THE FLOOR PLAN. THE COVER SHEET INDICATED THIS IS
 A NON-SPRINKLERED BUILDING AND 2 EXITS REQUIRED. SHEET
 A 5 THE FIXTURE PLAN SHOWS AN EXITING PLAN. IT WOULD
 APPEAR THAT THE NEW DOUBLE DOORS AND RAMP ARE TO BE
 PART OF THE MEANS OF EGRESS SINCE THE FLOOR PLAN SHOWS
 TRAVEL DISTANCES. THE RACK STORAGE BEHIND THE BANK OF
 SALES COUNTERS IS MOSTLY 10 FEET TALL AND CONSIDERED
 THE STORAGE AREA. PLEASE SHOW HOW COMPLIANCE WITH
 SECTION 1016.2.5 (2) OF THE 2020 FBC-B.
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHERE ALL
 OF THE FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA.
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM.
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE.
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44- INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY.
  
 3B) NOTICE ONLY. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 105.2.6. RACK STORAGE OVER 5FEET 9 INCHES TALL REQUIRES
 A SEPARATE RACK STORAGE PERMIT, WITH PLANS REVIEW, AND
 ASSOCIATED FEES.
  
 3C)2ND REQUEST, NOTE THAT E3 WAS NOT VERSIONED. SHEET
 A-5 THE FLOOR PLAN/ RACK STORAGE PLAN SHOW EXIT LIGHTS
 AND DIRECTIONAL EXIT LIGHTING. SHEET E3 THE LIGHTING
 PLAN, ONLY SHOWS THE EXIT LIGHTS AT THE FRONT EXIT AND
 STOCKROOM DOUBLE DOORS. THE SHEET E3 NEW EXIT DOORWAY
 IS NOT SHOWN NOR IS THE EXIT LIGHT.
  
 3D) SEMI-COMPLIED. SHEET A-1 NOW SHOWS A SECOND LINE ON
 EACH SIDE OF THE RAMP BUT DOES NOT PROVIDE A CROSS
 SECTION OF THE RAMP AND CURB SHOWING COMPLIANCE WITH
 2020 FBC-ACCESSIBILITY CODE SECTION 1012.10 EDGE
 PROTECTION FOR THE RAMP.
  
 1ST ROUND OF COMMENTS. THERE IS NOT ANY CURRENT RAMP
 DETAIL SHOWING THE HEIGHT OR WIDTH OF THE TOP AND
 BOTTOM LANDINGS NOR OF THE RAMP ITSELF. SINCE THE RAMP
 IS PART OF THE MEANS OF EGRESS TO THE PUBLIC WAY PLEASE
 SHOW DETAILS IN COMPLIANCE WITH THE 2020 FBC-B
 SECTIONS:
 1012.2 SLOPE
 1012.3 CROSS SLOPE.
 1016.2 LANDINGS. 1016.2.1 SLOPE, 1016.2 WIDTH, 1016.3
 LENGTH
 1012.8 POSSIBILITY OF HANDRAILS
 1012.10 EDGE PROTECTION FOR THE RAMP
  
 4) SHEETS D1 DEMO AND A-3 EXTERIOR ELEVATIONS SHOW ON
 THE FRONT OF THE BUILDING THE REMOVAL OF THE SPANDREL
 PANELS AND REPLACE WITH LARGE MISSILE IMPACT GLAZING.
 THE SIDE ELEVATION SHOWS NEW DOUBLE DOORS. PLEASE
 PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING:
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS. ROOF HATCH.
 (B) WINDOWS & MULLIONS.
  
 4A) THE ARCHITECTURAL SHEETS SHOW THE REAR DELIVERY
 DOOR/ EXIT DOOR AS A PAIR OF SWING DOORS. THE PRODUCT
 APPROVAL SUBMITTED FOR THE REAR DELIVERY DOOR IS A ROLL
 UP DOOR. IF A ROLL UP DOOR IS TO BE USED, THEN CORRECT
 THE ARCHITECTURAL SHEETS AND THE ROLL UP DOOR CANNOT BE
 USED AS A EGRESS DOOR.
  
 4B) THE PRODUCT APPROVAL FROM OLDCASTLE 12-0109.06 IS A
 MIAMI-DADE NOA THAT HAD EXPIRED NOV. 18/ 2014. PLEASE
 UPDATE.
  
 5) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) 2ND REQUEST, SEMI-COMPLIED. SHEET S0.1 PROVIDES THE
 WIND DESIGN CRITERIA BUT NOT THE PRESSURES FOR WALL
 ZONES 4 & 5 NOR THE ROOF ZONES 1,2 OR 3. DESIGN WIND
 PRESSURES TO BE USED FOR EXTERIOR COMPONENTS AND
 CLADDING MATERIALS SPECIFICALLY DESIGNED BY THE
 REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE
 DESIGN OF THE STRUCTURE, PSF. 2020FBC-B TABLE 1609.7(2)
 ADJUSTMENT FACTORS FOR HEIGHT & EXPOSURE. PROVIDE THE
 MEAN ROOF HEIGHT FOR THE BUILDING. ASCE 7-16 TABLE
 30.3.1. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 PLEASE NOTE FOR THE LOCATION THE VULT OF 168 WOULD
 EQUATE TO 130 VASD, NOT 144 VASD. IF THE DESIGNER OF
 RECORD WISHES TO DESIGN TO THE HIGHER DESIGN
 REQUIREMENTS YOU MAY, IT WILL EQUATE TO HIGH PSF PER
 SQUARE FOOT OF OPENING. CONVERT PRESSURES TO VASD.
  
 8) THIS REVIEW 2ND REVIEW THERE IS A ROOF TOP CURB BUT
 NOT A PRODUCT APPROVAL, NO TESTING REPORT .
 1ST ROUND OF COMMENTS. THE SUBMITTED ENGINEERED ROOF
 TOP CURB DOES NOT HAVE EITHER A MIAMI-DADE NOA LISTING
 NOR A FLORIDA APPROVAL, ALL PRODUCT APPROVALS WITHIN
 THE STATE OF FLORIDA ARE SUPPOSED TO HAVE 3RD PARTY
 QUALITY ASSURANCE PROGRAM IN AFFECT. LOCAL GOVERNMENT
 CAN HAVE THEIR OWN PROGRAM. THE CITY OF WEST PALM BEACH
 HAS THE SAME 10 CRITERIA AS THE STATE. 2020 FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, CURBS, ROOF TOP EXHAUST FANS,
 VENTILATORS ETC.
  
 9) BUILDING PROVISO: SHEET S1.1 SHOWS NEW STEEL SUPPORT
 ANGLES AND STEEL DECKING. THE DETAILS SHOW WHERE
 JOBSITE WELDING WILL BE REQUIRED FOR THE NEW ROOF TOP
 MECHANICAL EQUIPMENT.
  
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2020 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 10A) 2ND REQUEST. THEE RESPONSE FROM THE STRUCTURAL
 ENGINEER IS THAT A ROOF HATCH HAS BEEN ADDED TO SHEET
 S1.1
 THE COVERSHEET LISTS THE ROOFTOP DECK AT A HEIGHT OF 18
 FEET 3 INCHES. 2020 FBC-M 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE
 EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON
 AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH
 THAT PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET
 ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
  
  
 10B) 2ND REQUEST. 2017 FBC-B 1011.16 LADDERS. PERMANENT
 LADDERS SHALL NOT SERVE AS A PART OF THE MEANS OF
 EGRESS FROM OCCUPIED SPACES WITHIN A BUILDING.
 PERMANENT LADDERS SHALL BE PERMITTED TO PROVIDE ACCESS
 TO THE FOLLOWING AREAS:
 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE,
 REPAIR OR MONITORING OF EQUIPMENT.
 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE
 STAIRWAY ACCESS IN ACCORDANCE WITH SECTION
 1011.12.1.
 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 306.5 OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER