| 2021-03-30 12:36:15 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21020946 |
| | ADD: 1670 45TH ST. TENANT SUITE NUMBER???? / AUTO ZONE |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??? |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MARCH 29TH/ 2021 |
| | |
| | ACTION: DENIED |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) 2ND REQUEST. THE PERMIT APPLICATION NOR THE |
| | TITLEBLOCK PROVIDE THE TENANT SUITE/ UNIT ADDRESS. WHEN |
| | WE VIEW ( GOGGLE MAPS) THE ADDRESS OF 1670 45TH ST THIS |
| | IS FOR THE WHOLE SHOPPING CENTER, NOT THIS TENANT |
| | SPACE. |
| | |
| | 2020 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) SHEET A0- COVER: COMPLIED. |
| | |
| | 3) SHEET A-1 THE FLOOR PLAN: |
| | 3A) SEMI-COMPLIED. THIS FLOOR PLAN NOW SHOWS A NEW EXIT |
| | DOORWAY AT THE REAR OF THE BUILDING. THE QUESTION |
| | REMAINS IS THE EXIT SIGN MOUNTED TO THE WALL OR |
| | CEILING. AT WHAT HEIGHT IS THE CEILING, THE RACK |
| | STORAGE IS 7SEET 6 INCHES TALL. THE OTHER ISSUE IS THIS |
| | REVISED ARCHITECTURAL PLAN WAS NOT CARRIED OVER ONTO |
| | SHEET E3 THERE IS NO EXIT DOORWAY OR EXIT LIGHT SHOWN |
| | FOR THE NEW EXIT DOORWAY. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. CORELATE PLANS TO SHOW THE |
| | SAME DETAILS. |
| | |
| | 1ST ROUND OF COMMENTS. THERE IS NO LIFE SAFETY SHEET, |
| | JUST THE FLOOR PLAN. THE COVER SHEET INDICATED THIS IS |
| | A NON-SPRINKLERED BUILDING AND 2 EXITS REQUIRED. SHEET |
| | A 5 THE FIXTURE PLAN SHOWS AN EXITING PLAN. IT WOULD |
| | APPEAR THAT THE NEW DOUBLE DOORS AND RAMP ARE TO BE |
| | PART OF THE MEANS OF EGRESS SINCE THE FLOOR PLAN SHOWS |
| | TRAVEL DISTANCES. THE RACK STORAGE BEHIND THE BANK OF |
| | SALES COUNTERS IS MOSTLY 10 FEET TALL AND CONSIDERED |
| | THE STORAGE AREA. PLEASE SHOW HOW COMPLIANCE WITH |
| | SECTION 1016.2.5 (2) OF THE 2020 FBC-B. |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHERE ALL |
| | OF THE FOLLOWING ARE MET: |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA. |
| | |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM. |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE. |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44- INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY. |
| | |
| | 3B) NOTICE ONLY. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 105.2.6. RACK STORAGE OVER 5FEET 9 INCHES TALL REQUIRES |
| | A SEPARATE RACK STORAGE PERMIT, WITH PLANS REVIEW, AND |
| | ASSOCIATED FEES. |
| | |
| | 3C)2ND REQUEST, NOTE THAT E3 WAS NOT VERSIONED. SHEET |
| | A-5 THE FLOOR PLAN/ RACK STORAGE PLAN SHOW EXIT LIGHTS |
| | AND DIRECTIONAL EXIT LIGHTING. SHEET E3 THE LIGHTING |
| | PLAN, ONLY SHOWS THE EXIT LIGHTS AT THE FRONT EXIT AND |
| | STOCKROOM DOUBLE DOORS. THE SHEET E3 NEW EXIT DOORWAY |
| | IS NOT SHOWN NOR IS THE EXIT LIGHT. |
| | |
| | 3D) SEMI-COMPLIED. SHEET A-1 NOW SHOWS A SECOND LINE ON |
| | EACH SIDE OF THE RAMP BUT DOES NOT PROVIDE A CROSS |
| | SECTION OF THE RAMP AND CURB SHOWING COMPLIANCE WITH |
| | 2020 FBC-ACCESSIBILITY CODE SECTION 1012.10 EDGE |
| | PROTECTION FOR THE RAMP. |
| | |
| | 1ST ROUND OF COMMENTS. THERE IS NOT ANY CURRENT RAMP |
| | DETAIL SHOWING THE HEIGHT OR WIDTH OF THE TOP AND |
| | BOTTOM LANDINGS NOR OF THE RAMP ITSELF. SINCE THE RAMP |
| | IS PART OF THE MEANS OF EGRESS TO THE PUBLIC WAY PLEASE |
| | SHOW DETAILS IN COMPLIANCE WITH THE 2020 FBC-B |
| | SECTIONS: |
| | 1012.2 SLOPE |
| | 1012.3 CROSS SLOPE. |
| | 1016.2 LANDINGS. 1016.2.1 SLOPE, 1016.2 WIDTH, 1016.3 |
| | LENGTH |
| | 1012.8 POSSIBILITY OF HANDRAILS |
| | 1012.10 EDGE PROTECTION FOR THE RAMP |
| | |
| | 4) SHEETS D1 DEMO AND A-3 EXTERIOR ELEVATIONS SHOW ON |
| | THE FRONT OF THE BUILDING THE REMOVAL OF THE SPANDREL |
| | PANELS AND REPLACE WITH LARGE MISSILE IMPACT GLAZING. |
| | THE SIDE ELEVATION SHOWS NEW DOUBLE DOORS. PLEASE |
| | PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING: |
| | 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS. ROOF HATCH. |
| | (B) WINDOWS & MULLIONS. |
| | |
| | 4A) THE ARCHITECTURAL SHEETS SHOW THE REAR DELIVERY |
| | DOOR/ EXIT DOOR AS A PAIR OF SWING DOORS. THE PRODUCT |
| | APPROVAL SUBMITTED FOR THE REAR DELIVERY DOOR IS A ROLL |
| | UP DOOR. IF A ROLL UP DOOR IS TO BE USED, THEN CORRECT |
| | THE ARCHITECTURAL SHEETS AND THE ROLL UP DOOR CANNOT BE |
| | USED AS A EGRESS DOOR. |
| | |
| | 4B) THE PRODUCT APPROVAL FROM OLDCASTLE 12-0109.06 IS A |
| | MIAMI-DADE NOA THAT HAD EXPIRED NOV. 18/ 2014. PLEASE |
| | UPDATE. |
| | |
| | 5) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 7) 2ND REQUEST, SEMI-COMPLIED. SHEET S0.1 PROVIDES THE |
| | WIND DESIGN CRITERIA BUT NOT THE PRESSURES FOR WALL |
| | ZONES 4 & 5 NOR THE ROOF ZONES 1,2 OR 3. DESIGN WIND |
| | PRESSURES TO BE USED FOR EXTERIOR COMPONENTS AND |
| | CLADDING MATERIALS SPECIFICALLY DESIGNED BY THE |
| | REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE |
| | DESIGN OF THE STRUCTURE, PSF. 2020FBC-B TABLE 1609.7(2) |
| | ADJUSTMENT FACTORS FOR HEIGHT & EXPOSURE. PROVIDE THE |
| | MEAN ROOF HEIGHT FOR THE BUILDING. ASCE 7-16 TABLE |
| | 30.3.1. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | PLEASE NOTE FOR THE LOCATION THE VULT OF 168 WOULD |
| | EQUATE TO 130 VASD, NOT 144 VASD. IF THE DESIGNER OF |
| | RECORD WISHES TO DESIGN TO THE HIGHER DESIGN |
| | REQUIREMENTS YOU MAY, IT WILL EQUATE TO HIGH PSF PER |
| | SQUARE FOOT OF OPENING. CONVERT PRESSURES TO VASD. |
| | |
| | 8) THIS REVIEW 2ND REVIEW THERE IS A ROOF TOP CURB BUT |
| | NOT A PRODUCT APPROVAL, NO TESTING REPORT . |
| | 1ST ROUND OF COMMENTS. THE SUBMITTED ENGINEERED ROOF |
| | TOP CURB DOES NOT HAVE EITHER A MIAMI-DADE NOA LISTING |
| | NOR A FLORIDA APPROVAL, ALL PRODUCT APPROVALS WITHIN |
| | THE STATE OF FLORIDA ARE SUPPOSED TO HAVE 3RD PARTY |
| | QUALITY ASSURANCE PROGRAM IN AFFECT. LOCAL GOVERNMENT |
| | CAN HAVE THEIR OWN PROGRAM. THE CITY OF WEST PALM BEACH |
| | HAS THE SAME 10 CRITERIA AS THE STATE. 2020 FBC-B |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, CURBS, ROOF TOP EXHAUST FANS, |
| | VENTILATORS ETC. |
| | |
| | 9) BUILDING PROVISO: SHEET S1.1 SHOWS NEW STEEL SUPPORT |
| | ANGLES AND STEEL DECKING. THE DETAILS SHOW WHERE |
| | JOBSITE WELDING WILL BE REQUIRED FOR THE NEW ROOF TOP |
| | MECHANICAL EQUIPMENT. |
| | |
| | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| | FRAMING INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2020 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 10A) 2ND REQUEST. THEE RESPONSE FROM THE STRUCTURAL |
| | ENGINEER IS THAT A ROOF HATCH HAS BEEN ADDED TO SHEET |
| | S1.1 |
| | THE COVERSHEET LISTS THE ROOFTOP DECK AT A HEIGHT OF 18 |
| | FEET 3 INCHES. 2020 FBC-M 306.5 EQUIPMENT AND |
| | APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE |
| | EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON |
| | AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH |
| | THAT PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET |
| | ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN |
| | INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. |
| | |
| | |
| | 10B) 2ND REQUEST. 2017 FBC-B 1011.16 LADDERS. PERMANENT |
| | LADDERS SHALL NOT SERVE AS A PART OF THE MEANS OF |
| | EGRESS FROM OCCUPIED SPACES WITHIN A BUILDING. |
| | PERMANENT LADDERS SHALL BE PERMITTED TO PROVIDE ACCESS |
| | TO THE FOLLOWING AREAS: |
| | 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE, |
| | REPAIR OR MONITORING OF EQUIPMENT. |
| | 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE |
| | STAIRWAY ACCESS IN ACCORDANCE WITH SECTION |
| | 1011.12.1. |
| | 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 306.5 OF THE FLORIDA BUILDING CODE, |
| | MECHANICAL. |
| | |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |