| 2021-03-01 16:53:24 | 03/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A-2; |
| | |
| | A. PLEASE SHOW THE DRINKING FOUNTAIN IN FRONT OF THE |
| | TWO RESTROOMS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON THE DRINKING FOUNTAINS FIXTURE, PLEASE SHOW THE |
| | 30 X 48 IN. CLEAR FLOOR SPACE FOR A FORWARD APPROACH TO |
| | THE WHEELCHAIR PER THE 2020 FBC ACC SEC. 602.2 CLEAR |
| | FLOOR SPACE AND 305.5 POSITION. |
| | |
| | C. PLEASE SHOW THE CLEAR FLOOR SPACE AND DIMENSIONS FOR |
| | THE LAVATORY, TOILET, AND DRINKING FOUNTAIN ON DIAGRAM |
| | SEVEN PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR |
| | SPACE. THE CLEAR FLOOR SPACE SHALL BE 60" INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDEWALL, AND |
| | 56" INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER THE 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | D. PLEASE SHOW THE LOCATION OF THE WATER CLOSET FLUSH |
| | CONTROL PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS. |
| | |
| | E. PLEASE PROVIDE DETAIL SHOWING THE LAVS HEIGHT OF 34" |
| | INCHES MAXIMUM PER THE 2020 FBC ACC SEC. 606.3. |
| | |
| | F. THE TOILET PAPER DISPENSERS ON DIAGRAM EIGHT SHALL |
| | BE 7" INCHES MINIMUM AND 9" INCHES MAXIMUM IN FRONT OF |
| | THE WATER CLOSET MEASURED TO THE CENTERLINE OF |
| | DISPENSER PER THE 2020 FBC ACC SEC. 604.7. |
| | |
| | G. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | H. PLEASE SHOW TOILET 17" INCHES TO 19" INCHES MAXIMUM |
| | MEASURED TO THE TOP OF THE SEAT ON DIAGRAM EIGHT PER |
| | THE 2020 FBC ACC SEC. 604.4 SEATS. |
| | |
| | I. PLEASE PROVIDE A NOTE THAT THE SEAT SHALL BE OF THE |
| | HINGED OPEN-FRONT TYPE PER THE 2020 FBC P 425.3 WATER |
| | CLOSET SEATS. |
| | |
| | J. PLEASE SHOW THE WATER CLOSET ON DIAGRAM EIGHT, THE |
| | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE PER THE 2020 |
| | FBC ACC SEC. 604.2 LOCATION. |
| | |
| | K. A VERTICAL GRAB BAR IS NOT ALLOWED; GRAB BARS SHALL |
| | BE INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC |
| | ACC SEC. 609.4. |
| | |
| | L. IN DIAGRAM SEVEN, IT REFERS TO THE WATER FOUNTAIN |
| | ELEVATION OF 3/ A-2, AND IT SHOULD BE A-4; PLEASE |
| | CHANGE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | M. PLEASE SHOW THE REAR GRAB BAR LOCATION PER THE 2020 |
| | FBC ACC SEC. 604.5.2 REAR WALL. |
| | |
| | N. PLEASE PROVIDED DETAIL FOR GRAB BAR BACKING PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. ON SHEET P-2; |
| | |
| | A. THERE IS A BACKFLOW RPZ IN THE BUILDING. IS IT A |
| | CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW. IF SO, IT |
| | WILL BE REQUIRED AT THE WATER METER AND INSTALLED BY A |
| | LICENSED CONTRACTOR WITH A SEPARATE PERMIT. THIS RPZ |
| | WILL NEED TO BE CERTIFIED BY THE CITY OF WEST PALM |
| | BEACH UTILITIES DEPARTMENT ACCORDING TO THEIR CROSS |
| | CONNECTION CONTROL MANUAL PAGE 11 (C). IF THIS IS AN |
| | ISOLATION BACKFLOW, IT WILL BE REQUIRED TO BE CERTIFIED |
| | BY A LICENSED BACKFLOW CONTRACTOR. A REPORT MUST BE |
| | FILLED OUT AND BE WITH THE PERMIT AT FINAL AS THE |
| | INSPECTOR MUST TAKE FOR CITY RECORDS. PLEASE NOTE IF |
| | ISOLATION, A DRAIN WILL BE REQUIRED FOR THE BACKFLOW |
| | DISCHARGE AS AN INDIRECT WASTE. ALSO, CONTAINMENT |
| | BACKFLOW WILL NEED TO BE WITHIN 5 FEET FROM THE METER |
| | AND ACCESSIBLE. ANY DEVIATION WOULD HAVE TO BE APPROVED |
| | BY THE CITY OF WPB UTILITIES DEPARTMENT. |
| | |
| | B. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| | ASKING FOR THE FORM. |
| | |
| | C. PLEASE PROVIDE DETAIL FOR THE SLAB REPAIR PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON DIAGRAM ONE, THE DRINKING FOUNTAIN AND THE SINK |
| | CANNOT DISCHARGE INTO A HORIZONTAL WET VENT PER THE |
| | 2020 FBC SEC. P 912.1. |
| | |
| | E. ON DIAGRAM SEVEN, THE WATER CLOSET SAYS 1' 11", |
| | PLEASE REFER TO COMMENT ONE LETTER J FOR CORRECT |
| | SPACING PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. DRAIN TEMPERATURE RELIEF LINE SHALL DISCHARGE INTO |
| | THE DRAIN PAN, NOT THE MOP SINK PER THE 2020 FBC SEC. P |
| | 504.6(5). |
| | |
| | G. ON DIAGRAM NINE, PLEASE REMOVE URINAL AND ANY |
| | DETAILS ON THIS PAGE THAT DO NOT PERTAIN TO THESE PLANS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | H. ON DIAGRAM SIX, IT REFERS TO INSULATION; PLEASE GIVE |
| | THE THICKNESS AND R FACTOR ALONG WITH THE COMMENT THAT |
| | PIPE UNDERGROUND OR NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. |
| | |
| | 3. PLEASE PROVIDE A CONDENSATE DIAGRAM FOR HVAC UNITS |
| | OR SUBMIT DETAIL OF THE DRYWALL FOR THE CONDENSATE LINE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. CONDENSATE NEEDS |
| | TO BE 1' AWAY FROM THE 2020 FBC B1503.7 PROTECTION |
| | STRUCTURE AGAINST DECAY AND TERMITES. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |