| 2021-03-23 08:50:16 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21020896 |
| | 3/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P.1 & P.2: NO SIZING CALCULATIONS HAVE BEEN |
| | PROVIDED FOR THE GREASE WASTE LINE AND FUTURE GREASE |
| | INTERCEPTOR. INSTALLATION OF THE 3-INCH GREASE WASTE |
| | LINE WILL BE AT THE BUILDING OWNER'S AND CONTRACTOR'S |
| | RISK- SECTION 107.2.1 WPB. |
| | |
| | A) NOTE J INDICATES THE POINT OF CONNECTION OF THE |
| | GREASE WASTE LINE TO THE EXISTING BUILDING SEWER, |
| | HOWEVER THIS CONNECTION CANNOT BE MADE UNTIL THE FUTURE |
| | INTERCEPTOR IS INSTALLED. PLEASE REVISE THE NOTE TO |
| | INDICATE "FUTURE POINT OF CONNECTION"- SECTION 107.2.1 |
| | WPB. |
| | |
| | B) SHOW A TWO-WAY CLEANOUT AT THE JUNCTION OF THE DRAIN |
| | LINE AND SEWER JUNCTION- SECTIONS 708.1.3 & 708.1.8 FBC |
| | P. |
| | |
| | 2) P.1 & P.2: NOTE G INDICATES THE SANITARY LINES ABOVE |
| | THE CEILING WHICH APPEARS TO BE INCORRECT. DOES THE |
| | BUILDING HAVE A SECOND STORY? IF SO PLEASE PROVIDE A |
| | NOTE AND SYMBOL TO CLARIFY- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |