| Plan Review Notes For Permit 21020874 |
| Permit Number |
21020874 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-21 13:51:33 | STAIR SHOP DRAWINGS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) EXTERIOR STAIR IS SUBJECT TO WIND LOADS- PLEASE SHOW | | | THE WIND DESIGN CRITERIA TO COMPLY WITH FBC 1603.1.4 | | | 2) PLEASE PROVIDE THE STRUCTURAL CALCULATIONS FOR THE | | | STAIR DESIGN OR HAVE THE DRAWINGS SIGNED AND SEALED BY | | | A DESIGN PROFESSIONAL. FBC 107.2.1.2 | | | 3) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER AND SHOW | | | THE PRINTED NAME FBC 107.2.1 - FBC 107.1 | | | 4) INTERIOR STAIR DRAWING NEEDS TO SHOW THE ATTACHMENTS | | | TO THE STRUCTURE. FBC 107.2.1 |
|